User manual
Installation and commissioning
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
7
– Check connection with the device (menu “Device -> Check connection”)
– A new device can be configured immediately.
As soon as the parameter Protocol type (t.Pro) is changed and saved, the communication with the device is
interrupted. To enable the SMI2 configuration software to communicate with the device again, the “Factory
settings” mode must be temporarily activated.
5.4 Configuration check
After the RESET button is pressed for a short time, the display extinguishes for 3 seconds, and all current
parameters of the device are then displayed.
The parameters are presented in the following way:
– Parameter name (2 seconds),
– Parameter value (2 seconds),
– Pause (1 second),
– Next parameter.
The display order corresponds to the register number from the Table D3, column 2.
The RESET button must be pressed for a short time again to terminate the display of parameters.
5.5 “Factory settings” mode
In this mode the device works within the factory settings, whereby the parameters configured by the user are
saved and not overwritten. This function can be useful if the device must be configured and its network
parameters are unknown.
To activate this mode, press the RESET button for more than 2 s. The flashing word Fact is displayed and
the device accepts the factory settings (see Appendix D.1).
To disable the mode, the RESET button must be pressed again for more than 2 s or the command APLY
must be sent by the master. The flashing word Fact then fades out and the device resumes the user pa-
rameters. The factory settings are effective as long as Fact is displayed.
►
NOTICE
If the network parameters are queried in this mode, the values of the saved
user network parameters are returned, not the factory setting.