User manual
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
8
Fig. 6.2 Filter time constant
6.4 Square root function
The function is intended for transmitters with the square characteristic. To enable the
function set the parameter Sqrt = ON.
6.5 Error
Table 6.1 Displayed errors
Display
Possible cause
Remedy
Eг.1
Measured value error
Check the input signal.
Check the sensor and
connection lines.
Contact the Technical
Support of akYtec GmbH.
LLLL
Measured value is below the lower limit for the
selected signal (see Table 2.2)
Check the input signal
HHHH
Measured value is above the upper limit for the
selected signal (see Table 2.2)
Check the input signal
|----|
Sensor break or short circuit
Check the signal line
Er.Cj
CJC sensor error
Contact the Technical
Support of akYtec GmbH.
7 Programming
Table 7.1 Function buttons
Key
Description
Press > 3 s:
– enter the programming
mode
– exit the programming
mode
Press < 1 s:
– save the parameter
+
Press > 3 s:
– enter the service menu
Increase value or menu
navigation
Decrease value or menu
navigation
– Press and hold the button or to activate the ramp function while changing
parameter.