– if no button was pressed within 20 s, the device returns to the operating mode
automatically.
Table 7.2 Programming parameters
Name Display Parameter Valid value Description Default
SP.Lo
SP.Lo
Setpoint lower limit -999...9999
affected by di.P
0
SP.Hi
SP.Hi
Setpoint upper limit -999...9999
affected by di.P
30
Cnt
Cnt
Control function
oFF
OFF
U
Heat
Heating
CooL
Cooling
U
Alarm outside limits
П
Alarm within limits
in.t
in.t
Input signal See Table 2.2 Pt100
td
td
0B
Filter time constant
0…10 s
0
out.E
out.E
Output safe state
ON
OFF
OFF
di.Lo
di.Lo
Signal lower limit* -999...9999
affected by di.P
0
di.Hi
di.Hi
Signal upper limit* -999...9999
affected by di.P
100
SQrt
SQrt
Square root function
ON
OFF
OFF
di.P
di.P
Decimal point
----
0000
---.-
---.-
000.0
--.--
00.00
-.---
0.000
2u3u
2u3u
RTD connection
3-Ln
3-wire
3-Ln
2-Ln
2-wire
d.FnС
d.FnС
Alarm function
ON
OFF
OFF
* only for linear signals
Table 7.3 Service menu
Display Comments Valid values
гES
Restore factory settings
0
User settings
1
Factory settings
CLbг
Service function -
t.C
Service function -
SCj
Service function
SoFt
Firmware version
Note:
1. The minus sign is displayed in the most significant digit, together with 1. The display
range is -199.9...999.9 if di.P = ---.-,
2. When setting the signal limits, take into account that in some cases the correct value
cannot be displayed though there is no error indication.
Example 1:
di.Lo: -999 -> 4 mA di.Hi: 9999 -> 20 mA
For the input current of 3.8 mA the correct indication should be “-1068”. Actually “1068”
will be displayed.