ITP16 Temperature indicator User guide ITP16_2018.05_0280_EN © All rights reserved Subject to technical changes and misprints akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.
Contents 1 Overview ........................................................................................................................................................ 2 2 Specifications ................................................................................................................................................ 2 2.1 Galvanic isolation ..................................................................................................................................... 3 2.
1 Overview ITP16 is a universally applicable process indicator and can be used with various input signals: RTD, TC, linear voltage signal. The device requires 24V DC auxiliary voltage. It is designed for control and monitoring of industrial processes. 2 Specifications ITP14 can be ordered in two versions. They differ in the display color. Ordering key: Table 2.1 Technical data Power supply Power consumption, max. Input Input signal Sampling time, max.
1000M Measurement range, °C -180…+200 Temperature coefficient, °C-1 0.00428 1000P -200…+850 0.00391 Display Signal type c.1E3 P.1E3 n1E3 Ni1000 -60…+180 TC according to IEC 60584-1:2013 K –200…+1300 tP.KA tP.J tP.n tP.t tP.S tP.r tP.b tP.A1 J –200…+1200 N –200…+1300 T –250…+400 S –50…+1750 R –50…+1750 B +200…+1800 0.00617 - A 0…+2500 TC according to GOST 8.585 L -200…+800 tP.L tP.A2 tP.
3 Intended use The device may only be used in the manner described in this user guide, properly installed and in accordance with the specification. Damages caused by disregarding the instructions of this manual are without liability. Non-observance of the safety guidelines may result in damage to the device and injury to personal. Improper use Any other use is considered improper.
5...7 Fig. 5.2 Connecting the wire to the terminal Fig. 5.1 Wire preparation Do not use wire end ferrules to connect stranded wires. To connect solid wire, push the wire into the terminal. To connect fine-stranded wire, tin the wire end. To connect stranded wire, press the release lever and push the wire into the terminal. Fig. 5.3 Disconnecting the wire Press the release lever to free the wire. Fig. 5.4 Mounting – The electrical connections are shown in Fig. 5.5-5.
Fig. 5.7 Voltage signal wiring Table 5.1 Terminal assignment Designation 24VDC 24VDC + DODO+ AI1 AI2 AI3 Description Power supply Output Output + + (three-wire RTD) + – Table 5.2 Sensor cables Sensor type Cable length, max. Resistance (each wire), max. RTD 100 m 30 ohm TC 20 m 100 ohm 5.1.
− − − − Heating Cooling Alarm within limits Alarm outside limits The safe output state can be selected in the parameter out.E. Note: Switching hysteresis: 0.05 x (SP.Hi – SP.Lo). 6.2 Alarm If the control function Cnt is set and the alarm function d.FnC = ON, the display blinks with a frequency of about 2 Hz when the output is switched on (see Fig. 6.1). Fig. 6.1 6.
Fig. 6.2 Filter time constant 6.4 Square root function The function is intended for transmitters with the square characteristic. To enable the function set the parameter Sqrt = ON. 6.5 Error Table 6.1 Displayed errors Display Possible cause Eг.1 Measured value error LLLL Measured value is below the lower limit for the selected signal (see Table 2.2) Measured value is above the upper limit for the selected signal (see Table 2.2) HHHH Remedy Check the input signal.
– if no button was pressed within 20 s, the device returns to the operating mode automatically. Table 7.2 Programming parameters Name Display SP.Lo SP.Lo SP.Hi SP.Hi Parameter Valid value Description Default Setpoint lower limit -999...9999 affected by di.P 0 Setpoint upper limit -999...9999 affected by di.P 30 oFF Heat CooL U П OFF Heating Cooling Alarm outside limits Alarm within limits U Cnt Cnt Control function in.t in.t Input signal td td See Table 2.
Example 2: di.Lo: -999 -> 4 mA di.Hi: 9999 -> 20 mA For the input current of 20.8 mA the correct indication should be “10548”. Actually “0548” will be displayed. Fig. 7.1 Device menu 8 Maintenance The maintenance includes: – – – cleaning the housing and the terminals from dust, dirt and debris checking the fastening of the device checking the wiring (connecting leads, fastenings, mechanical damage) The device should be cleaned with a damp cloth only.
9 Transportation and storage Pack the device in such a way as to protect it reliably against impact for storage and transportation. The original packaging provides optimum protection. If the device is not taken immediately after delivery into operation, it must be carefully stored at a protected location. The device should not be stored in an atmosphere with chemically active substances. Permitted storage temperature: -25…+55 °C ► NOTICE The device may have been damaged during transportation.