5.1 Wiring
CAUTION
Switch on the power supply only after the wiring of the device has been completely
performed
NOTICE
Switch off the device before checking the sensor and connection lines.
For circuit integrity check use only the measuring device with the output voltage max.
4.5 V to prevent the device damage. Disconnect the sensor in case of higher voltage.
NOTICE
Signal cables should be routed separately or screened from the supply cables.
Only a shielded cable may be used for signal lines.
Fig. 5.1 Wire preparation
Fig. 5.2 Connecting the wire to the terminal
Do not use wire end ferrules to connect
stranded wires.
To connect fine-stranded wire, tin the wire
end.
To connect solid wire, push the wire into the
terminal.
To connect stranded wire, press the release
lever and push the wire into the terminal.
Fig. 5.3 Disconnecting the wire
Press the release lever to free the wire.
Fig. 5.4 Mounting
The electrical connections are shown in Fig. 5.5-5.7, the terminal assignments in Table
5.1.
Ensure that the device is provided with its own power supply line and electric fuse I = 0.5
A.
Solid conductor cross-section: 0.2…0.8 mm². Stranded conductor cross-section:
0.45…0.7 mm². Wires should be stripped for approx. 8 mm.