Instructions
Table Of Contents
4 Configuration and programming
10
akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de
Parameter
Data type
Modbus
function
Address (hex)
Address
(dec)
Ac-
cess
AI4 status (digital
mode)
BOOL
0x01, 0x02
0x1013 4115 R
DO1…DO8, F1, F2
status bitmask
BOOL
0x01, 0x02,
0x05, 0x0F
0x0000 – 0x0009 0–9
RW**
UINT16
0x03, 0x04,
0x06, 0x10
0x0000 0 RW**
Network variables
BOOL
0x01, 0x02,
0x05, 0x0F
0x2000 – 0x23F0 8192 – 9200 RW
UINT16
0x03, 0x04,
0x06, 0x10
0x0200 – 0x023F 512 – 575 RW
Seconds UINT16
0x03, 0x04,
0x06, 0x10
0x0400 1024 RW
Minutes UINT16
0x03, 0x04,
0x06, 0x10
0x0401 1025 RW
Hours UINT16
0x03, 0x04,
0x06, 0x10
0x0402 1026 RW
Day
UINT16
0x03, 0x04,
0x06, 0x10
0x0403 1027 RW
Month UINT16
0x03, 0x04,
0x06, 0x10
0x0404 1028 RW
Year UINT16
0x03, 0x04,
0x06, 0x10
0x0405 1029 RW
Weekday
UINT16
0x03, 0x04,
0x06, 0x10
0x0406 1030 R
Week of month UINT16
0x03, 0x04
0x0407 1031 R
Calender week UINT16
0x03, 0x04
0x0408 1032 R
* Used for network data exchange using network variables
DP = Decimal point offset (Sect. 4.3.1)
AIx INT = AIx REAL × 10 DP (sect. 4.3.1)
For outputs DP = 4 (constant)
** Output status can be only written via network in I/O mode (sect. 6.4)