TRUE, if the communication with PRM is established and the modification of PRM matches
the one specified in the project
FALSE, if the communication with the module is lost or the modification of PRM does not
match the one specified in the project
2. Output safe statethe parameter can be set for each output using the itemOutputs \ Digi-
tal’ in the configuration tree. The parameter defines the safe output state if communication with
PR200 has been interrupted.
3. Debouncing filterthe parameter is available only for inputs of PRM-24. It can be set for
each input using the itemInputs \ Digital’ in the configuration tree. The parameter defines the
input filter time for contact bounce suppression and can be set in the range of 0…255 ms.
NOTICE
It is not recommended to use the contact bounce suppression for input signals with a fre-
quency above 90 Hz and a duty cycle of 50% or less. A useful signal can be missed.
5.1 Firmware update
When communication between akYtec ALP software and PR200 with PRM(s) connected is estab-
lished, you can check all devices for firmware update. If a firmware update is available, it will be
prompted to install it on the basic device and the modules.