Instructions
PR200 
Programmable relay 
PR200_0029_EN 
© All rights reserved. Subject to technical changes and misprints. 
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany 
Tel: +49 (0) 511 16 59 6720 · www.akytec.de 
Electrical connections 
Fig. 4 Terminal blocks 
Table 6 Terminal assignment 
№  Designation  Function  №  Designation  Function 
1 
AC230V L / 
DC24V - 
Power supply AC / DC *  
21 
DO5  Digital output DO5 
2 
AC230V N / 
DC24V + 
Power supply AC / DC * 
22 
-  Common contact DO5...DO6 
3 
COM1  Common minus pole DI1...DI4 
23 
DO6  Digital output DO6 
4 
DI1  Digital input DI1 
24 
DO7  Digital output DO7 
5 
DI2  Digital input DI2 
25 
-  Common contact DO7...DO8 
6 
DI3  Digital input DI3 
26 
DO8  Digital output DO8 
7 
DI4  Digital input DI4 
27 
AI1  Analog input AI1 
8 
COM2  Common minus pole DI5...DI8 
28 
COM3  Common minus pole AI1...AI2 
9 
DI5  Digital input DI5 
29 
AI2  Analog input AI2 
10 
DI6  Digital input DI6 
30 
AI3  Analog input AI3 
11 
DI7  Digital input DI7 
31 
COM4  Common minus pole AI3...AI4 
12 
DI8  Digital input DI8 
32 
AI4  Analog input AI4 
13 
OUT 24V+  24 V DC integrated voltage source 
33 
RS-485 D-  RS485 Port1 D- 
14 
OUT 24V-  24 V DC integrated voltage source 
34 
RS-485 D+  RS485 Port1 D+ 
15 
DO1  Digital output DO1 
35 
RS-485 D-  RS485 Port2 D- 
16 
-  Common contact DO1...DO2 
36 
RS-485 D+  RS485 Port2 D+ 
17 
DO2  Digital output DO2 
37 
AO1- / V- 
see Table 7 
18 
DO3  Digital output DO3 
38 
АО1+ / V+ 
see Table 7 
19 
-  Common contact DO3...DO4 
39 
АО2- / АО1 
see Table 7 
20 
DO4  Digital output DO4 
40 
АО2+ / АО2 
see Table 7 
* Depending on the device modification (PR200-230 or PR200-24) 
Table 7 Terminal assignment 
only PR200-230(24).2.2  only PR200-230(24).4.2 
№  Designation  Function  №  Designation  Function 
37  АО1- 
Analog output AO1 (4-20 mA) 
37  V-  Auxiliary voltage -24 VDC 
38  АО1+  38  V+  Auxiliary voltage +24 VDC 
39  АО2- 
Analog output AO2 (4-20 mA) 
39  АО1  Analog output AO1 (0-10 V) 
40  АО2+  40  АО2  Analog output AO2 (0-10 V) 
a 
b 
Fig. 5 Connecting switch contacts to digital inputs: a) PR200-24, b) PR200-230  Fig. 6 Connecting 3-wire sensors with PNP 
transistor outputs 
►
NOTICE 
Supply voltage for outputs may not exceed 30 V. 
a 
b 
c 
Fig. 7 Wiring of analog inputs: a) 4-20 mA, b) 0-10 V, c) resistors (up to 4000 ohm) 
►
NOTICE 
Wire the terminals only when the device is powered off. 
a 
b 
Fig. 8 Relay outputs 
Fig. 9 Wiring of analog outputs: a) 4-20 mA (PR200-X.2), b) 0-10 V (PR200-X.4) 
Fig. 10  Disconnecting terminal blocks 
Fig. 11 Removing PR200 from the 
DIN rail 
Removal 
1.  Take off the terminal blocks without disconnecting the 
wires (Fig. 10) 
2.  Insert a screwdriver into the eyelet of the slide interlock 
(Fig. 11) 
3.  Loosen the slide interlock pushing the screwdriver in the 
direction of the arrow 1, and then remove the relay from the DIN 