35
4.7 Calibration
Only general information about calibration of analog inputs or outputs is given in this sec-
tion. For detailed information about calibration refer to the user guide of the device.
If calibration of analog inputs or outputs is necessary, use the menu item Device > Cali-
bration….
The item is active only if a device is connected. Select the calibration target (inputs or out-
puts) in the opened dialog.
Fig. 4.26
After the calibration target selection, the execution of the program in the device is
stopped. The program starts again upon the successful completion of the calibration.
4.7.1 Input calibration
To calibrate inputs, connect a reference signal source to them. Start calibration, select the
type of signal connected to the input and set the calibration parameters in the opened di-
alog.
Fig. 4.27 PR200 input calibration
Use the item Reset settings to apply the default settings for calibration.
Use the list Select input to select the input to calibrate, click the button Next and follow
the instructions.
4.7.2 Output calibration
Before calibrating an analog output, prepare the appropriate measuring device, than start
calibration and follow the instructions. Measure the signal at the output indicated at the
top right of the window and enter the value in the input field.