Fig. 4 Terminal blocks
Table 6 Terminal assignment
№ Designation Function № Designation Function
1
AC230V L /
DC24V -
Power supply AC / DC *
21
DO5 Digital output DO5
2
AC230V N /
DC24V +
Power supply AC / DC *
22
- Common contact DO5...DO6
3
COM1 Common minus pole DI1...DI4
23
DO6 Digital output DO6
4
DI1 Digital input DI1
24
DO7 Digital output DO7
5
DI2 Digital input DI2
25
- Common contact DO7...DO8
6
DI3 Digital input DI3
26
DO8 Digital output DO8
7
DI4 Digital input DI4
27
AI1 Analog input AI1
8
COM2 Common minus pole DI5...DI8
28
COM3 Common minus pole AI1...AI2
9
DI5 Digital input DI5
29
AI2 Analog input AI2
10
DI6 Digital input DI6
30
AI3 Analog input AI3
11
DI7 Digital input DI7
31
COM4 Common minus pole AI3...AI4
12
DI8 Digital input DI8
32
AI4 Analog input AI4
13
OUT 24V+ 24 V DC integrated voltage source
33
RS-485 D- RS485 Port1 D-
14
OUT 24V- 24 V DC integrated voltage source
34
RS-485 D+ RS485 Port1 D+
15
DO1 Digital output DO1
35
RS-485 D- RS485 Port2 D-
16
- Common contact DO1...DO2
36
RS-485 D+ RS485 Port2 D+
17
DO2 Digital output DO2
37
AO1- / V-
see Table 7
18
DO3 Digital output DO3
38
АО1+ / V+
see Table 7
19
- Common contact DO3...DO4
39
АО2- / АО1
see Table 7
20
DO4 Digital output DO4
40
АО2+ / АО2
see Table 7
* Depending on the device modification (PR200-230 or PR200-24)
Table 7 Terminal assignment
only PR200-230(24).2.2 only PR200-230(24).4.2
№ Designation Function № Designation Function
37 АО1-
Analog output AO1 (4-20 mA)
37 V- Auxiliary voltage -24 VDC
38 АО1+ 38 V+ Auxiliary voltage +24 VDC
39 АО2-
Analog output AO2 (4-20 mA)
39 АО1 Analog output AO1 (0-10 V)
40 АО2+ 40 АО2 Analog output AO2 (0-10 V)
a
b
Fig. 5 Connecting switch contacts to digital inputs: a) PR200-24, b) PR200-230 Fig. 6 Connecting 3-wire sensors with PNP
transistor outputs
►
NOTICE
Supply voltage for outputs may not exceed 30 V.
a
b
c
Fig. 7 Wiring of analog inputs: a) 4-20 mA, b) 0-10 V, c) resistors (up to 4000 ohm)
►
NOTICE
Wire the terminals only when the device is powered off.
a
b
Fig. 8 Relay outputs
Fig. 9 Wiring of analog outputs: a) 4-20 mA (PR200-X.2), b) 0-10 V (PR200-X.4)
Fig. 10 Disconnecting terminal blocks
Fig. 11 Removing PR200 from the
DIN rail
Removal
1. Take off the terminal blocks without disconnecting the
wires (Fig. 10)
2. Insert a screwdriver into the eyelet of the slide interlock
(Fig. 11)
3. Loosen the slide interlock pushing the screwdriver in the
direction of the arrow 1, and then remove the relay from the DIN