Fig. 10.4
Circuit program
The circuit program can be implemented in the way shown in Fig. 10.5.
Fig. 10.5
Input I1 connected to the switch SA1 “MODE”
Input I2 connected to the button SB1 “START”
Input I3 connected to the button SB2 “STOP”
Input I6 connected to the overload switch F1
Input I7 connected to the button SB3 “RESET
Input I8 connected to the button SB4 “TEST”
Output Q1 connected to the motor
Output Q2 connected to the acoustic signal HA1
Output Q3 connected to the signal lamp HL1
Program description:
1. Input I2 (SB1 “START”)