Instructions

Device configuration
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
30
Retries, max. the number of the failed request attempts before query is stopped
and the status of the device changes. The valid range is 0255.
Burst request group request of consecutive registers to increase the data through-
put
Status variable select a BOOL variable using the icon to record the device sta-
tus:
o 1 the device functions properly
o 0 the device is not connected.
Start query select a BOOL variable using the icon to control the query:
o 0 query disabled
o 1 query enabled.
Change register order determines the register order in two-register variables
Change byte order determines the byte order in the register
Comment the text comment to describe the device
Fig. 4.12 Query time diagram
The list of the variables to be requested from this slave is in the lower part of the window.
Each variable created in this list can be found in the variable table under the tab Net-
work, Slot X with a separate list of variables (sect. 5.5) for each slave device.
Add a variable by clicking the icon New variable, and set its properties.
Fig. 4.13 Variable configuration in master mode
Name the name of the variable
Type the data type of the variable: BOOL, INT or REAL
Register the register address
Bit the number of the bit of the register (0…15) (only for BOOL variables)
Read function / Write function selection of the read / write function or disable
reading / writing.
Number of registers the number of registers occupied by the variable (only for INT
variables)