Instructions
Configuration
Use in: AKO-55424 / AKO-555241 / AKO-555242 / AKO-558241 / AKO-558242
Step 1:
Once the pushbutton has been connected, connect the power supply of the station. Before 2 minutes have passed,
press the “AUTOCONFIG” pushbutton 5 consecutive times.
Step 2:
Press the “AUTOCONFIG” pushbutton for 5 seconds; the alarm will emit 5 short tones. Configuration is completed.
For a correct detection of inputs, all devices must be correctly connected and in NO ALARM mode, including
the devices connected in digital inputs.
Once configured, the display shows the indicator corresponding to the device detected at each input in green:
Luminous pushbutton
Use in: AKO-55323 / AKO-55123 / AKO-55120
The unit is supplied as ready-to-use; no configuration is required
Operation
Activating the alarm Deactivating the alarm
Press the alarm pushbutton Slightly rotate the alarm pushbutton in the clockwise
direction.
x5
ON
OFF
1
2
5"
Maintenance
Clean the surface of the unit with a soft cloth, water and
soap.
Do not use abrasive detergents, petrol, alcohol or
solvents, as this might damage the sensor.
Technical specifications
Power supply......................................15 Vdc ± 3 Vdc
Working ambient temperature............-50 ºC to 50 ºC
Storage ambient temperature .............-50 ºC to 70 ºC
Protection degree ..............................................IP 65
Installation category .................................................II s/
EN 61010-1
Pollution degree....................................II s/ EN 61010-1
Maximum pushbutton wiring distance ..................300 m
Dimensions ......202 mm (W) x 82 mm (H) x 84.4 mm (D)