Specifications
OM-229 158 Page 23
Backlight − press the Increase or Decrease button to turn LCD display backlight On or Off.
The factory default is On.
Isolation Detect− press the Increase or Decrease button to enable or disable this feature.
The factory default is Yes.
All parameters in System Setup are considered global, and any changes to the system set-up parameters will apply to all programs.
To reset the system back to factory default settings, turn off the power source, and wait until the display goes blank. Turn on the power source. When
the display lights, press and hold the Increase and Decrease buttons. A message will display Press Program to reset factory
defaults. Release the Increase and Decrease buttons, and press the Program button.
6-4. Programming
Programming allows the operator to setup a program for a particular heating process. The selections available are Timed, Remote, or Manual.
6-4-1. Time-Based Control
Time-based control operates the system and controls the heating process based on programmed time and power, voltage, current, or energy values.
An auxiliary relay can also be programmed to interface with a PLC or similar controller.
Press the Program button to access the programming mode. Use the cursor button to move the cursor between Program, Segement, Type, Power,
and Time.
Mode...: Timed
Program: 1 Segment: 1
Type...:>Power Level
Power..: 0.0 KW Time: 00:00:00
The default position of the cursor is next to Program. Press the Increase or Decrease button.
Use the Cursor button to move the cursor to the desired selection, and press the Increase or Decrease button to
change the value to the desired setting.
Possible selections Timed:
Program: 1 − 8 Segement: 1 − 10
Type: Power Level, Slope, KW Seconds, End
Power: 0.0 − 35 or Voltage: 0.0 − 700, or Current: 0.0 − 700 Time: 00:00:00 − 99:59:59 or infinity
6-4-2. Remote Control
If Remote was selected as the control mode in the setup window, the following screen appears for programming: