Installation manual
SeaMach 24 VDC
Rooftop Air Conditioners
SeaMach 24 VDC Rooftop Air Conditioner Installation Manual 5/2013  Page 20 of 20
1976A520 (10-11) PP
Chapter 11 - Maintenance
One of the biggest advantages to your air conditioner is that the maintenance needed to keep the unit in 
good care is minimal. As the owner, your primary responsibility is the cleaning and replacement of the 
lter(s). Filters are made from long life natural bers which can be cleaned and reused.
If the lters are not cleaned at regular intervals, they may become partially clogged with lint, dirt, grease, 
etc. A clogged lter will produce a loss of air volume and may eventually cause an icing-up of the cooling 
(evaporator) coil. The lters should be cleaned or changed at least every two weeks when the air conditioner 
is in operation.
Cleaning and/or changing the lters:
Disengage the two 1/4-turn fasteners that secure the ceiling assembly grille to the ceiling assembly 1. 
(See Figure 7).
Lower the grille and lter(s) from the ceiling assembly.2. 
Take lter(s) out and either clean or exchange with other lters (See Figure 7).3. 
If the vehicle is equipped with a  ush mount ceiling assembly,  remove the four return air grill 4. 
screws.
Remove lter from grill and either clean or exchange with new lter. 5. 
NOTE: If replacement lters are necessary, they can be purchased from most Authorized Service 
Centers. It is recommended that spare lters be carried with the unit at all times to replace worn, 
torn or deteriorated lters.
Service Person:
Electrical  -A.    All  electrical  work  and/or  inspection  should  be  performed  only  by  qualied  service 
personnel. Contact your nearest Service Center if electrical problems should arise.
Check  Points  -B.    Failure  to  start  or  to  cool  the  air  are  sometimes  problems  with  air  conditioning 
units. The air conditioner is designed to operate on 24 VDC electrical power.  If the compressor on 
the air  conditioner fails  to start,  check with  your  Service  Center  to determine  that the  proper wire 
size  is  connected  to  the  unit,  the  proper  circuit  breakers  are  installed  as  protection  devices  on  the 
electrical  circuit.  Refer  to  the  chart  on  page  9  to  determine  if  the  proper  size  wire  is  being  used. 
Each  air  conditioning  unit  must  be  protected  with  a  50  amp  time  delay  fuse  or  circuit  breaker. 
If the air conditioner continues to trip off the circuit breakers, have an electrician check the starting 
amperage and running amperage on the unit.  If the circuit breaker continues to trip off and the electrical 
consumption is found to be normal, it will require the replacement of the faulty circuit breaker. If all 
electrical power to the air conditioner is normal but neither the fan nor the compressor will operate, 
the connector plug located behind the ceiling assembly control box should be checked to determine 
whether it is faulty.
Mechanical Integrity -C.   The air conditioner should be inspected periodically to be sure that the bolts 
which  secure  the  unit  to  the  roof  are  tight  and  in  good  shape. Also,  an  examination  of  the  plastic 
shroud covering the air conditioner on the top of the roof should be made periodically. Be sure the four 
mounting screws and washers are snug and holding the shroud to the air conditioner. Also examine the 
shroud to be sure it is not developing cracks or has suffered damage from impact.
Airxcel, Inc.
Marvair Division
156 Seedling Dr.
Cordele, GA 31015










