Specifications
  8
  IF OTHER THAN NON-METALLIC 
  CABLES ARE USED FOR SUPPLY 
  CONDUCTORS, APPROPRIATE STRAIN 
  RELIEF CONNECTORS OR CLAMPS 
  SHOULD BE USED. 
  IN NO CASE SHOULD CLAMPING OR 
  PINCHING ACTION BE APPLIED TO  
  THE INDIVIDUAL SUPPLY LEADS 
  (NEUTRAL AND “HOT” WIRES). 
3.  Connect high voltage supply leads to the control box 
  wire leads with provided wire nuts.  “Hot” connects 
  to black lead, “neutral” to white lead and “ground” 
  to green lead. 
4.  Gently fold all wiring into the electrical box while 
  verifying that it is not either pinched or cut. 
5.  Complying with the warnings listed below, connect 
  the 115 VAC supply wiring to its power source. Be 
  sure all power remains off until beginning checkout 
  procedure. 
DANGER 
TO PREVENT THE POSSIBILITY OF SHOCK INJURY 
FROM APPLIANCE OPERATION: 
THE WHITE WIRE MUST BE CONNECTED TO 
NEUTRAL IN THE SERVICE BOX ENTRANCE AND 
THE MECHANICAL GROUND MUST BE 
CONNECTED TO A GROUNDING LUG IN THE 
SERVICE BOX OR THE MOTOR GENERATOR 
COMPARTMENT. 
IMPORTANT 
When connecting the 115V electrical conduit: 
1.  Make any adjustments required to relieve 
  pinched or stressed wiring. 
2.  Verify that the “ridged” side of both plugs are 
  properly aligned. Verify that the connectors 
  have snapped together on both sides. Do not 
  use excessive force when joining the connectors. 
CONNECT THERMOSTAT WIRING 
A.  Ceiling Plenum Connections 
1.  Bring the thermostat wiring previously routed into 
  the roof opening to the low voltage terminal board 
  extending from the front of the ceiling plenum 
  electrical box. 
  These low voltage ceiling plenum designations 
  complete the following circuits: 
  B  -12 VDC for all relay coils 
  Y  +12 VDC for compressor relay coil 
  GH  +12 VDC for hi fan relay coil 
  GL  +12 VDC for low fan relay coil 
  W  +12 VDC for heat relay – found on 
    heat ready boxes 
CHART 1 
Ceiling Plenum
Low Voltage Wire
Designations
Wall Thermostat
Control Wiring
Mate With
B Blue
Y  Yellow
GH   Green
GL Gray
W   White
  After completion of high and low voltage wiring, 
  replace the wirebox cover. 
B.  Mounting the Wirebox (See Figure 2) 
1.  Two machine screws are on the upper units. The 
  control box will be mounted by positioning the 
  control box over the screws and using the wing 
  nuts to fasten the control box to the upper unit. 
  Installation in a 47000 series unit will require 
  mounting the control box with the wires exiting 
  upwards (See Figure 4). 
2.  Insert the freeze circuit thermistor probe into the roof 
  top unit evaporator coil. Verify that the probe is 
  located in the coil properly (See Figure 2). 
The  optional  heater  assembly  may  now  be  installed. 
Refer to Figures 2 and 3 for the 48000 and 49000 
series units.  Refer to Figure 5 for the 47000 series 
units. 
  Position the heater assembly into the return air 
opening as shown (for 48000 and 49000 series). 
The heater bracket must be installed between the 
  basepan and the plastic drain pan. See Figure 3. 
  Tighten set screw to secure the assembly so as to 
  prevent movement. The 47000 series installation 
  will use wing nuts to secure the heater as in 
  Figure 5.  
Insert the two-pin connector of the heater 
  umbilical into the receptacle on the control box. 
  Insure that the connector snap-locks into position. 










