Specifications
Electrical Control Function   
92  Electrical Control System 
-1.0
-2.0
-3.0
-4.0
0.0
T1-Ts+ΔT
L
(H+-L)*0.4+L
(H+-L)*0.6+L
-5.0
-6.0
-6.5
H+
(H+-L)*0.8+L
(H+-L)*0.6+L
(H+-L)*0.2+L
For Cassette & Duct: 
When the compressor is on, the indoor fan can be set to high, medium, low and auto. And the anti-cold wind 
function has the priority. 
Auto fan action: 
-3.5
T1-Ts-ΔT
-4
High
Low
-5
Medium
-4.5
1.3.3.4 Prevent Over-Heating   
In  heating  mode, when  the  indoor  unit has  no  capacity requirement due to  indoor  room  temperature 
increased, the Indoor fan will run in super breeze. (Anti-cold wind function has the priority) 
1.3.3.5 Defrosting mode: 
Condition of defrosting: 
If any one of the following items is satisfied, AC will enter the defrosting mode. 
After the compressor starts up and keeps running, mark the minimum value of T3 from the 10th minutes to 
15th minutes as T30. 
1)If the compressor cumulate running time is up to 29 minutes and T3< TCDI1, T3+T30SUBT3ONE≦T30. 
2)If the compressor cumulate running time is up to 35 minutes and T3< TCDI2, T3+T30SUBT3TWO≦T30. 
3)If the compressor cumulate running time is up to 29 minutes and T3< TCDI3 for 3 minutes. 
4)If the compressor cumulate running time is up to 120 minutes and T3<-15℃. 
Condition of ending defrosting: 
If any one of the following items is satisfied, the defrosting will finish and the machine will turn to normal 
heating mode. 