Specifications
  Electrical Control Function 
Electrical Control System  91 
T4
E DC_FAN_SSLOW_SPD_ADD
D DC_FAN_SLOW_SPD_ADD
C DC_FAN_MIN_SPD_ADD
B DC_FAN_MID_SPD_ADD
A DC_FAN_HI_SPD_ADD
21℃
19℃
18℃
16℃
15℃
13℃
12℃
10℃
1.3.3.3 Indoor fan running rules: 
For HKD,HND, Console 
In  heating  mode,  indoor fan can  be  selected  as  high,  medium,  low,  auto  and  silent.  The anti-cold-wind 
function has the priority.   
When the compressor is running, the indoor fan is controlled as below: 
If the compressor stops caused by the room temperature rising, the indoor fan will be forced to run 127 
seconds with breeze. During this period, the anti-cold-wind is disabled.   
Auto fan action in heating mode: 