Specifications
  Wrench torque sheet for installation 
Installation  75 
1. Wrench torque sheet for installation 
Outside diameter 
Torque 
Additional tightening torque 
mm 
N.cm 
N.cm 
Ф6.35 
1500(153kgf.cm) 
1600(163kgf.cm) 
Ф9.52 
2500(255kgf.cm) 
2600(265kgf.cm) 
Ф12.7 
3500(357kgf.cm) 
3600(367kgf.cm) 
2.  Connecting the cables 
The power cord of connect should be selected according to the following specifications sheet. 
Rated current of appliance 
Nominal cross-sectional area (mm²) 
>3 and ≤6 
0.75 
>6 and ≤10 
1 
>10 and ≤16 
1.5 
>16 and ≤25 
2.5 
The cable size and the current of the fuse or switch are determined by the maximum current indicated on the 
nameplate which located on the side panel of the unit. Please refer to the nameplate before selecting the 
cable, fuse and switch. 
3.  Pipe length and the elevation 
Maximum piping length and height difference 
1 drive 2 
1 drive 3 
1 drive 4 
1 drive 5 
Max. length for all rooms (m) 
30 
45 
60 
75 
Max. length for one IU (m) 
20 
25 
30 
30 
Max. height difference 
between IU and OU (m) 
OU higher than IU 
10 
10 
10 
10 
OU lower than IU 
15 
15 
15 
15 
Max. height difference between IUs (m) 
10 
10 
10 
10 
Additional refrigerant charge 
1 drive 2 
1 drive 3 
1 drive 4 
1 drive 5 
Chargeless pipe 
length (m) 
10 
15 
20 
25 
Additional 
refrigerant charge 
(g) 
15 x (length for all 
rooms - 10) 
15 x (length for all 
rooms - 15) 
15 x (length for all 
rooms - 20) 
15 x (length for all 
rooms - 25) 
Caution: 
●  Refrigerant pipe diameter is different according to indoor unit to be connected. When using the 
extension pipe, refer to the tables below. 
●  When refrigerant pipe diameter is different from that of outdoor unit union (for 18K indoor unit), additional 
transfer connector needs to be used on outdoor unit union. 