Specifications
  Troubleshooting 
Electrical Control System  121 
2.4.2.8 Temperature protection of compressor discharge(ODU P4) 
Temperature protection of 
compressor discharge
Check whether the 
compressor discharge temp. 
is more than 115°C ?
Check whether the wiring 
connection is right between 
compressor discharge temp. 
sensor and PCB according 
to wiring diagrams?
Method: Check whether the 
resistance of compressor 
discharge temp. sensor is 
right refer to the Appendix 2
No
Yes
Yes
Trouble is solved
No
Judge: The 
discharge temp. 
sensor is broken
Check whether the 
refrigerant is leak
Correct the wiring connection
Stop leaking and add refrigerant
Replace the compressor discharge temp. sensor
No
Yes
Replace outdoor main board
Yes