Service manual
  ELECTRONIC FUNCTION 
HKD  DCI                                                                42                                                           Version      -  1 
Meanwhile, the maximum frequency is limited by the indoor fan speed. 
Indoor fan speed 
Maximum frequency 
High speed/8 degree heating/ turbo function 
No limit 
Medium speed 
FHeatMaxMidFan 
Low speed/sleep mode 
FHeatMaxLowFan 
Silent mode 
Fixed at F3 
If  users  switch  on  AC  by  remote  controller,  the  compressor  will  run  at  the  Fmax  frequency  for  7 
minutes according to outdoor ambient temp. During the 7 minutes, the frequency limitation is active. 
7 minutes later, the compressor running frequency will be controlled as below: 
+5.0
+4.5
+3.5
+3.0
+2.5
+2.0
+1.5
T1-Ts+ΔT
+1.0
I
G
F
E
D
C
B
A
+0.5
+4.0
H
J
While the zones of A,B,C... are corresponding to different compressor running frequency. 
ΔT=0℃  as default. 
Note: 
When T1-Ts keeps in the same temp. zone for 3 minutes, the compressor will run as the below rules: 
A: Increase the frequency to 3 grade higher until to FREMAX. 
B~E: Increase the frequency to 2 grade higher until to FREMAX. 
F~G: Increase the frequency to 1 grade higher until to FREMAX. 
H: Keep the current frequency. 
I: Decrease the frequency to the 1 grade lower until to F1. 