  ELECTRONIC FUNCTION 
HKD  DCI                                                                40                                                           Version      -  1 
The auto fan acts as below rules: 
a
b
c
d
5.0
4.0
2.5
1.0
6.0
T1-Ts
e
H
(H-L)*0.75+L
(H-L)*0.5+L
(H-L)*0.25+L
L
9.4.2.4 Condenser temperature protection 
---55℃<T3<60℃, the compressor frequency will decrease to the lower level until to F1 and then runs 
at F1.If T3<54℃, the compressor will keep running at the current frequency. 
---T3<52℃, the compressor will not limit the frequency and resume to the former frequency. 
---T3>60℃  for 5 seconds, the compressor will stop until T3<52℃. 
9.4.2.5 Evaporator temperature protection 
---T2<0℃, the compressor will stop and restart when T2>=5℃. 
---0℃≦T2<4℃, the compressor frequency will be limited and decreased to the lower level 
---4℃≤T2≤7℃, the compressor will keep the current frequency. 
---T2>7℃, the compressor frequency will not be limited. 