LVD - Low Voltage Disconnect circuit is open (battery is disconnected, red)
BATT - Battery test passed (green)
FAULT - General alarm fault (red-continuous), Faulty rectifier (red-blinks)
BATT TEST - Manual battery test, use a pencil tip to initiate
ALARM OFF - Silences the internal buzzer, use a pencil tip
RESET - Resetting the controller, use a pencil tip
RS232 - Connector for the host
8.6.2. Main Functions
The 1004 system controller supports these functions:
1)
RS232 communication with a host
2) Controlling dual-LVD for managing two branches of batteries. LVD voltages are
settable and nonvolatile
3) Boost/Float charging, voltages are settable and nonvolatile
4)
Battery test for two branches
5) Three dry-contacts for alarm, user-defined
6)
Audio-visual alarm
7) LED's indicators for AC, DC, LVD, battery and general fault
8)
Optional: 2x3 digits display for system voltage/current metering
9) Faulty rectifier detection
10)
Open breakers detection (any of them)
11) LVD bypass activation alarm