User's Manual Part 2b
Installing the BSPS Hardware Installation Guide
7-14 Airspan Networks Ltd. 02030311-05
3
4
2 1
Figure 7-7: Method of interconnection between monoblocs
9. Protect the terminals of the monoblocs using suitable battery grease.
10. Before connecting the BSPS battery cables to the battery ensure that the battery
isolation circuit breakers are in the
OFF position.
11. Connect the red lead of the BSPS battery cables to the positive terminal on
monobloc 4.
12. Connect the black lead of the BSPS battery cable to the negative terminal on
monobloc 1.
Battery 1
connection
Battery 2
connection