605-0000-593 AS4000 / AS4020 Base Station Installation and Commissioning Release 7.
Table Of Contents Installation.............................................................................................................................1 Overview AS4000........................................................................................................... 1 Overview AS4020........................................................................................................... 3 Preparation .............................................................................................
Printed Documentation Setting the System into Service .................................................................................. 127 AS4020 CT Setup and Test ........................................................................................... 128 AS4020 Menu Map..................................................................................................... 128 AS4020 error messages .............................................................................................
Installation Overview AS4000 AS4000 System The system uses Point-to-Multipoint digital radio links between the individual customer's premises and the carriers local "point of presence" typically the Local Exchange premises. If greater flexibility or range is required, the network radio equipment can be located in another suitable building or wayside cabinet.
Printed Documentation 2
Installation Overview AS4020 AS4020 System The system uses Point-to-Multipoint digital radio links between the individual customer's premises and the carriers local "point of presence" typically the Local Exchange premises. If greater flexibility or range is required, the network radio equipment can be located in another suitable building or wayside cabinet.
Printed Documentation Preparation Preparatory Tasks Installation Tools and Equipment The following lists of tools and equipment are required to successfully install and test the AS4000 Access Concentrator Racks. Required Tools Combination Spanners: 8 mm, 13 mm, 17 mm, & 19 mm. Spirit Level: 18 inch. Pozidrive: No 1 x 75 mm. No 2 x 100 mm ;No 3 x 150 mm. Screwdriver, flat blade: 3 mm x 100 mm. Screwdriver, flat blade: 5.5 mm x 100 mm. Screwdriver, flat blade: 8 mm x 150 mm.
Installation Air conditioning is installed and funtional (if required to maintain room environment). Adequate grounding is provided. Access to the equipment room will be adequate for normal handling and movement. Adequate lighting is available for carrying out the installation. Any non compliance with acceptable standards should be bought to the customers attention and resolved before proceeding with the installation.
Printed Documentation Note: It is recommended that one package carton of each type is retained should it be required to return any faulty or damaged items for repair.
Installation Rack Installation Rack Layouts AS4000 Racks AS4000 Central Terminal and Access Concentrator Racks are produced with the following layouts: Access Concentrator One DA Access Concentrator Shelf and a Fuse and Alarm Panel Two Access Concentrator Shelves and a Fuse and Alarm Panel 7
Printed Documentation Central Terminal Demand Assignment System One DA Modem Shelf with RF Combiner Shelf Two DA Modem Shelves with RF Combiner Shelf Expansion Rack with one DA Modem Shelf and a Fuse and Alarm Panel. (Connects to an existing Central Terminal Rack) Expansion Rack with two DA Modem Shelves and a Fuse and Alarm Panel.
Installation No of Modem Shelves 1 2 3 4 Central Terminal Rack 1 Modem Shelf 2 Modem Shelves 2 Modem Shelves 2 Modem Shelves Expansion Rack Not required Not required 1 Modem Shelf 2 Modem Shelves Integrated Basestation The Integrated Basestation incorporates a Combiner Shelf , Modem Shelf and Access Concentrator in a full height equipment rack.
Printed Documentation 10
Installation Rack Layouts AS4020 Racks AS4020 Central Terminal racks are produced with the following layouts: Central Terminal Systems using AS4020 Full height rack with RF Combiner Shelf. two AS4000 Modem Shelves and one AS4020 Modem Shelf Full height rack with RF Combiner Shelf, one AS4000 Modem Shelves and up to three AS4020 Modem Shelves Compact rack with RF Combiner Shelf.
Printed Documentation 12
Installation Rack Installation Positioning and Securing Racks Installing Rack in a Suite From the site survey, confirm the position of the CT Rack(s). If the racks are to be positioned in a suite, metalwork will be required to secure it to the overhead structure. Either a proprietary system or fabricated steelwork will be required - see site survey. Manoeuvre the racks into position.
Printed Documentation Typical Overhead Ironwork Support Note: In installations where threaded droprods in excess of 500mm are employed it may be necessary to provide additional support bars to ensure rigidity of the support structure. Securing a Rack to a Wall If the rack is to be positioned against a wall, attach two right-angled wall brackets to the top of the rack and finger tighten with the provided M12 screws. Manoeuvre the racks into position against the wall.
Installation DC Power and Alarm Cabling Rack Earthing Using the site survey, locate the building central [safety] grounding point. Run an earth cable rated at 30A to each rack and connect it to the centre earth stud located at the top or at the side of the rack. (only one external earth per rack) See illustrations below. These points are labelled with the IEC Earth symbol. Rack earthing at top Rack earthing at base Other external safety earth connections must not be made to the rack.
Printed Documentation Terminate the battery feed and return cables at the isolator/fuse positions, and ensure that the AC rack is isolated until the commencement of commissioning tests. DC Power The cables for the negative DC battery feeds, the 0V returns and the Rack Ground are detailed in. Should local requirements specify otherwise, it is acceptable for cables of other colours to be used, however, under no circumstances should the cable sizes be less than that specified in.
Installation Power Supply Configurations Three alternative methods are possible to connect the DC supply to the rack. Secure Supply: This is the preferred method as it provides DC from different sources giving greater resilience of supply than the other methods. (see diagram above and note 2 below) From each Distribution Boards (DB) run and tie in a negative battery feed and a zero volt return to a Dual Pole Isolating switch and then from the isolating switch to the AC/CT rack installed.
Printed Documentation Dual Supply: Both feeds are fed from the same Distribution Boards (DB) and separately fused so that in the event of one fuse failing the rack is supplied via the other fuse. Run and tie in two negative battery feeds and a two zero volt returns from the Distribution Board to a Dual Pole Isolating switch and then from the isolating switch to the to the AC/CT rack installed. These supplies should be rated at 30A. Power cables must be run and tied separate from signal cables.
Installation Remove clear plastic cover protecting the DC input terminals. Trim cables and strip 7mm. Crimp a spade terminal or terminal ring onto the wire and attach to terminals inside the Fuse and Alarm panel at the appropriate connection points. The negative supplies go to Termination Block 1 & 4. The positive battery returns go to 2 & 5. Replace clear plastic cover protecting the DC input terminals. DC Termination on Fuse and Alarm Panel.
Printed Documentation AS4000 AC Rack Cabling and Wiring AC Rack E1 Cabling 75 ohm Access Concentrator Interface Panel All cabling to the access concentrator connects to the interface panel. Slots 4,5 and 6 can be used for 75ohm and 120ohm connections. Slots 7-14 is used for 120ohm connections each slot will support up to 8 E1 connections.
Installation b) E1 Cabling (Switch Link) From the site survey, confirm the location of the Digital Distribution Frame (DDF) if a DDF is to be used or the Switch if the E1 feeds are fed directs to the equipment. The length of E1 feeds should not exceed 250 metres. Note: This must be a SELV port of an EN 60950 approved product. Run the E1 cables from the AC shelf to the allocated positions on the DDF.
Printed Documentation Type 43 Backplane Adapter b. Siemens 1.5/6.5 Connector. Fit Siemens 1.5/6.5 Connector to 25way D-type adapters 303-1139-900 to the backplane sockets and terminate all cables with Siemens 1.5/6.5 connectors (75ohm ) and fit according to the figure below.
Installation Typical 75ohm DDF Layout 23
Printed Documentation 24
Installation AC Rack E1 Cabling 120 ohm Access Concentrator Interface Panel All cabling to the access concentrator connects to the interface panel. Slots 4,5 and 6 can be used for 75ohm and 120ohm connections. Slots 7-14 is used for 120ohm connections each slot will support up to 8 E1 connections. Access Concentrator Interface Panel (1026 Board) 120 ohm Cabling Specification In installations with 12Oohm cabling Double screened, 120Ohm, 8 twisted pairs.
Printed Documentation Note: This must be a SELV port of an EN 60950 approved product. Run the E1 cables from the AC shelf to the allocated positions on the DDF. In partial equipped installations it may be appropriate to run enough cables to cater for a complete rack of equipment. This reduces the need to disturb original installation when adding additional equipment. Feed the E1 cables through the top hole on the most convenient side of the rack, and down the front of the rack.
Installation Pair 1 Designation A1 B1 In In Screen 2 A2 A3 In In Screen 3 A3 B3 In In Screen 4 A4 B4 In In Pin Pair Designation 1 5 A5 Out 15 2 B5 Out 16 14 Screen 4 6 Pin 3 A6 Out 18 5 B6 Out 19 17 Screen 7 A7 Out 21 8 B7 Out 22 20 Screen 10 11 7 6 8 9 A8 Out 24 B8 Out 25 27
Printed Documentation Screen 23 Overall Screen Screen 13 120 ohm connections slots 4-6 Pair Designation 1 A1 B1 In In Screen 2 A2 A3 In In Screen 3 A3 B3 In In Screen 4 A4 B4 In In Screen Overall Screen Pin Pair Designation Pin 1 5 A5 Out 15 2 B5 Out 16 14 Screen 4 6 3 A6 Out 18 5 B6 Out 19 17 Screen 7 A7 Out 21 8 B7 Out 22 20 Screen 10 7 6 8 9 A8 Out 24 11 B8 Out 25 23 Screen 12 13 120 ohm connections slots 7-14 (In) Pair Designation 1
Installation B1 In Screen 2 A2 In A3 In Screen 3 A3 In B3 In Screen 4 A4 In B4 In Screen Overall Screen 2 B5 14 Screen 4 16 3 A6 In 18 5 B6 In 19 17 Screen 7 6 In A7 In 21 8 B7 In 22 20 Screen 10 7 6 8 9 A8 In 24 11 B8 In 25 23 Screen 12 13 120 ohm connections slots 7-14 (Out) Pair 1 Designation A1 B1 Out Out Screen 2 A2 A3 Screen Out Out Pin Pair Designation 1 5 A5 Out 15 2 B5 Out 16 14 Screen 4 6 Pin 3 A6 Out 18 5 B6
Printed Documentation 3 A3 B3 Out Out Screen 4 A4 B4 Screen Overall Screen 30 Out Out 7 A7 Out 21 8 B7 Out 22 20 Screen 10 7 A8 Out 24 11 B8 Out 25 23 Screen 13 8 9 12
Installation AC Rack T1 Cabling All cabling to the Access Concentrator connects to the interface panel. Slots 7, 8, and 9 can be used for T1 CTU connections. Slots 10-14 are used for T1 XTU connections each slot will support up to 8 T1 connections. (Exceptionally slots 4, 5, and 6 can be used for XTU connections using an adapter 303-1113-900 connected to the D- type below the BNCs for the relevant slot. Only T1 5-8 are available for T1 connections.
Printed Documentation Fit the RJ45 adapter 303-1112-900 and secure to the Backplane using screws in the top and bottom holes of the adapter. RJ45 adapter 303-1112-900 b) T1 Cabling (Switch Link) From the site survey, confirm the location of the Digital Distribution Frame (DDF) if a DDF is to be used or the Switch if the T1 feeds are fed directs to the equipment. The length of T1 feeds should not exceed 100 metres. Run the T1 cables from the AC shelf to the allocated positions on the DDF.
Installation PTU to Host Cabling RJ45 to DB25 Adaptor To connect the 100baseT cable to the AC Shelf interface panel a RJ45 to DB25 adaptor must be fitted. Fit the RJ45 to DB25 adaptor and screw to the backplane. The RJ45 to DB25 adaptor currently must be connected onto the lower of the two 25-way AC connectors allocated to each slot (even though the activity lights work if connected to the top).
Printed Documentation AC Rack Labeling The racks should be labelled as shown below.
Installation Interface Connections This page contains miscellaneous interface and connector details.
Printed Documentation 120 Ohm Interface Connections on DA Access Concentrator Backplane Interface Adaptor EIA 530 to V35 Interface Adapter EIA 530 to X21 EIA 530 loopback Connector 36
Installation 37
Printed Documentation BNC Terminations to Coax 38
Installation Type 43 Terminations to Coax 39
Printed Documentation 40
Installation Access Concentrator Card Installation The AC rack is shipped with shelves fitted to customer requirements and internal cabling complete. Warning: Before handling any cards or modules, observe full anti-static precautions. See Operations an Maintenance Guide Preliminary In a new installation ensure that the AC Circuit on the Fuse and Alarm panel are set to the OFF position (down).
Printed Documentation The maximum 64k build configuration (V5.1/CAS/ISDN) is shown above. The XTU functions are configured using Sitespan. V5.1 does not support Data XTUs. The maximum 32k build configuration for V5.2 is shown above. The XTU functions are configured using Sitespan. a. The load sharing PSUs go in slots 1&2. b. The Shelf Controller goes in slot 3. c. 42 All other slot positions are configurable via Sitespan.
Installation d. 3 CTUs are supported. Each CTU supports four CT modem shelves. Each CTU may be cabled for four 120 E1s or four 75 E1s. and are placed in slots 4, 5, and 6 e. XTUs (CAS, Data, ISDN, V5.1, V5.2 and PTU) are supported. Each XTU may be cabled for eight 120 E1s. These can be placed in slots 5-14.(It is preferable to build from slot 7 leaving 5 and 6 available for additional CTUs if required) f. CU cards may go in any unused slot. (slots 15& 16 are preferred as they have no E1 connections.
Printed Documentation c) All other slot positions are configurable via Sitespan. d) 3 CTUs are supported. Each CTU supports four CT modem shelves. Each CTU may be cabled for eight 120 T1s. and are placed in slots 7, 8, and 9 e) XTUs (GR303, CAS, Data, ISDN, V5.1, V5.2 and PTU) are supported. Each XTU may be cabled for eight 120 E1s. These can be placed in slots 8-14.(It is preferable to build from slot 10 leaving 8 and 9 available for additional CTUs if required) and in slots 4,5 and 6.
Installation AS4000 CT Shelf Cabling and Wiring Central Terminal Rack E1 Cabling 75 ohm From the site survey, confirm the location of the Digital Distribution Frame (DDF) if a DDF is to be used or the Backhaul/Access Concentrator if the E1 feeds are fed directs to the equipment. The length of E1 feeds should not exceed 250 metres Note: This must be a SELV port of an EN 60950 approved product.
Printed Documentation 75 Ohm Shelf Interface Connections Run the E1 co-axial cables from the modem shelf to the allocated positions on the DDF/Backhaul. (Two cables per shelf in normal working, four cables per shelf in protected mode). In partial equipped installations it may be appropriate to run enough cables to cater for a complete rack of equipment. This reduces the need to disturb original installation when adding additional equipment.
Installation Shelf Interface Panel 303-1111-900 75 Ohm Shelf Interface Connections Run the E1 co-axial cables from the modem shelf to the allocated positions on the DDF/Backhaul. (Two cables per shelf in normal working, four cables per shelf in protected mode). In partial equipped installations it may be appropriate to run enough cables to cater for a complete rack of equipment. This reduces the need to disturb original installation when adding additional equipment.
Printed Documentation 48
Installation CT Rack E1 Cabling 120 ohm From the site survey, confirm the location of the Digital Distribution Frame (DDF) if a DDF is to be used or the Backhaul/Access Concentrator if the E1 feeds are fed directs to the equipment. The length of E1 feeds should not exceed 250 metres Note: This must be a SELV port of an EN 60950 approved product.
Printed Documentation 120 Ohm Shelf Interface Connections Run the E1 120 ohm cables from the modem shelf to the allocated positions on the DDF/Backhaul. In partial equipped installations it may be appropriate to run sufficient cables to cater for a complete rack of equipment. This reduces the need to disturb original installation when adding additional equipment. Feed the E1 cables through the top left-hand side of the rack, and down the front of the rack.
Installation Run the E1 cables from the modem shelf to the allocated positions on the DDF/Backhaul. In partial equipped installations it may be appropriate to run sufficient cables to cater for a complete rack of equipment. This reduces the need to disturb original installation when adding additional equipment. Feed the E1 cables through the top left-hand side of the rack, and down the front of the rack. Identify and label each cable at both ends as well as the DDF/Backhaul positions.
Printed Documentation Tie in cables as necessary using suitable cable ties, trim, leaving no sharp edges. E1 Shelf Interface Connections To D-Type Plug Terminate all cables at the modem shelf end with 25 pin D-Type connectors. Terminate as detailed below.
Installation CT Rack T1 Cabling From the site survey, confirm the location of the Digital Distribution Frame (DDF) if a DDF is to be used or the Backhaul/Access Concentrator if the T1 feeds are fed directs to the equipment. The length of T1 feeds should not exceed 100 metres. Cat 5 FTP screened (foil & braid) twisted pair cable should be used.
Printed Documentation T1 (RJ45) interface connections to 303-1111-900 shelf interface panel Run the T1 cables from the modem shelf to the allocated positions on the DDF/Backhaul. In partial equipped installations it may be appropriate to run enough cables to cater for a complete rack of equipment. This reduces the need to disturb original installation when adding additional equipment. Feed the T1 cables through the top left-hand side of the rack, and down the front of the rack.
Installation The illustration below shows connections to Modem Shelves 2,3 and 4 using adapter 3031113-900 Tie in cables as necessary using suitable cable ties, trim, leaving no sharp edges.
Printed Documentation Baseband connections between CT and Expansion Racks Inter-rack Baseband connections to Expansion Rack Remove the blank panel located immediately below the combiner shelf on the CT Rack Run a Baseband ribbon cable from each modem shelf in the Expansion Rack to the combiner shelf via the hole created by the removal of the breakout sections during the rack installation.
Installation Expansion Rack Cabling Central Terminal Expansion Rack Cabling 2Mbit/s Cabling From the site survey, confirm the location of the Digital Distribution Frame (DDF) if a DDF is to be used or the Backhaul/Access Concentrator if the 2Mbit/s feeds are fed direct to the equipment. The length of 2Mbit/s feeds should not exceed 250 metres Note: This must be a SELV port of an EN 60950 approved product.
Printed Documentation 1. Shelf Interface Connections. 75 Ohm Connections Run the 2Mbit/s co-axial cables from the modem shelf to the allocated positions on the DDF/Backhaul. (Two cables per shelf in normal working, four cables per shelf in protected mode). In partial equipped installations it may be appropriate to run enough cables to cater for a complete rack of equipment. This reduces the need to disturb original installation when adding additional equipment.
Installation 120 ohm connection to CT modem shelf. Connect the 2Mbit/s ports on the DDF to E5 slot 5 connectors on shelf interface connections located on the modem shelf interface panel. If using protected mode connect the other 2Mbit/s cables to E5 slot 9 connectors on the same panel. Ensure that the respective 2Mbit/s ports have been configured on the DDF/Backhaul Tie in cables as necessary using suitable cable ties, trim, leaving no sharp edges.
Printed Documentation Antenna Configurations AS4000 This section describes the various antenna configurations and modifications needed to the baseband wiring if the AS4000 CT rack is configured so that the two modem shelves serve separate directional antenna. and the subsequent connection arrangements when an expansion rack is fitted. 1.
Installation 1. Remove the blank panel located immediately below the Combiner Shelf on the DA Rack. 1. Swap the baseband connectors from Modem Shelves 2 and 3 on the Combiner Shelf backplane (the sockets are located behind the switches on the Combiner Shelf). AS4020 This section describes the various antenna configurations and connections needed to the baseband wiring 1.
Printed Documentation Combiner Shelf Ribbon Connections Standard Config Mixed AS4000 / AS4020 Configuration for AS4020 where AS4000 exists on sectored /dual omni antenna 62
Installation Configuration for AS4020 where AS4000 exists on single omni and additional antenna added Integrated Base Station Rack The antenna is configured as shown in the diagrams below.
Printed Documentation 64
Installation Interface Connections This page contains miscellaneous interface and connector details.
Printed Documentation 120 Ohm Interface Connections on DA Access Concentrator Backplane Interface Adaptor EIA 530 to V35 Interface Adapter EIA 530 to X21 EIA 530 loopback Connector 66
Installation 67
Printed Documentation CT Rack Labelling Central Terminal Rack 68
Installation BNC Terminations to Coax 69
Printed Documentation Type 43 Terminations to Coax 70
Installation 71
Printed Documentation Central Terminal Card Installation The CT rack is shipped with shelves fitted to customer requirements and internal cabling complete. Preliminary In a new installation ensure that the CT Circuit Breakers located on the lower assembly of the Combiner Shelf are set to the OFF position (Down). See and that the breakers on the Fuse and Alarm panel of the Expansion Rack are switched are set to the OFF position (down) See.
Installation Expansion Rack Fuse and Alarm Panel Ensure that the end of suite fuses are adequately rated and insert these into the respective fuse holder positions. Card Insertion Insert the cards into the shelves, recording the serial numbers and revision status in the test form.
Printed Documentation Card Insertion DA Rack Card Insertion Expansion Rack 74
Installation Card Provision for New Installation With the initial installation it is advisable to install the cards in both the combiner shelf and the modem shelves with the power switched off.
Printed Documentation Insert the following modules and secure: 1 RF Power Amplifier Module (2 PA’s) in the left hand position in the combiner shelf 1 x Low Noise Amplifier + Diplexer (DIP/LNA 1) (Terminate output with 50ohm termination.
Installation Insert the following cards into each Modem Shelf: 2 x PSUs Slots 1 and 2. 1 x Analogue Card (AU) Slot 16. 1 x Demand Assignment Tributary Card (DTU). Slot 5. 1 x Shelf Controller (SC) Slot 3. Modem Cards Slots 10 to 15. Fit RF Coupler for using a DACU Fit RF Coupler for connection of systems to the DA Control Unit for commissioning. A 30dB coupler should be fitted to the male N-Type connector at the top of the DIP/LNA1 and the DIP/LNA2 (if fitted).
Printed Documentation Some Installations may use directional antennas and use two DIP/LNAs for a two shelf system. in this situation Shelf 1 connects to DIP/LNA 1 and Shelf 2 to DIP/LNA 2. See Hybrid Rack Modification for Directional Antenna Two Antenna Installations In new installations the protective boots of the antenna feeder tails free ends should be kept in position until the tail is actually connected.
Installation 2 x PSUs. Slots 1 and 2. 1 x Shelf Controller Card 1 x Analogue Card (AU). Slot 16. 1 x Demand Assignment Tributary Card (DTU). Slot 5. Modem Cards Slots 10 to15. b) Shelf 2 (CT Rack) or Shelf 4 (Expansion Rack) When installing cards into an existing installation the power is already connected and the cards should be inserted in the order listed below.
Printed Documentation AS4020 CT Shelf Installation and Cabling Shelf Connections AS4020 comprises of a single 65mm (approximately 1.5u) high shelf, which can be fitted in an ETSI rack, 19" rack or 21" rack. AS4020 is flexible in its deployment, although is must remain within a couple of meters of the radio sub-system. Initially the AS4020 CT shelf is fitted within the AS4000 CT rack with the Radio sub-system, and optionally alongside up to two AS4000 CT shelves.
Installation 1. Remove the blanking plate by removing the two screws that secure it to the chassis 2. Carefully slide the option board into the shelf ensuring that the connector mates with the backplane. 3. Secure with screws to the chassis.
Printed Documentation AS4020 Shelf Installation upgrade into AS4000 Rack This topic covers the installation of AS4020 shelves as an upgrade into an existing AS4000 rack. The AS4020 fits immediately below the combiner shelf in the central terminal rack. If more than one AS4020 is to be installed existing modem shelves will need to be removed. The AS4020 installation wiring diagrams in this manual should be used in conjunction with this topic. Parts required.
Installation inserted in J13 by removing the PSU from the third position and carefully inserting the hand into the gap. If there is difficulty removing the plig it is possible to loosen the switch assembly with the power still on but extreme care must be taken to avoid short circuiting the DC supply wiring. 6. If the rack is powered down remove the two screws retaining the supply switch panel on the combiner self to gain access to the combiner shelf back plane.
Printed Documentation 12. Fit the cable tray immediately above the AS4020 shelf. Fix the shelf with two cross head screws and locking washers. 13. Connect the IDC end of the combiner monitor connecting lead (454-0010-134) to the IDC connector in the cable assembly 454-0010-137 added in step 8. 14. Connect part no 454-0010-135 to the 26way high density D-type labeled 'Radio' on the front panel of the AS4020 15.
Installation Adding one AS4020 shelf to existing rack The following installation diagrams show the additions to wiring that need to be made when adding 1 AS4020 shelf into existing rack.
Printed Documentation Adding two AS4020 shelves to existing rack The following installation diagrams show the additions to wiring that need to be made when adding 2 AS4020 shelves into existing rack.
Installation Adding three AS4020 shelves to existing rack The following installation diagrams show the additions to wiring that need to be made when adding 3 AS4020 shelves into existing rack.
Printed Documentation Adding four AS4020 shelves to existing rack The following installation diagrams show the additions to wiring that need to be made when adding 4 AS4020 shelves into existing rack.
Installation Adding two AS4020 with two AS4000 If it is required to put two AS4020 shelves into an existing two shelf AS4000 installation the first AS4020 shelf should be placed between the combiner shelf and the top AS4000 shelf. To provide the second AS4020 shelf it is necessary to remove the bottom vent panel and move the lower AS4000 shelf down to accommodate the second AS4020 shelf below the top AS4000 shelf. The shelves should be cabled as shown below.
Printed Documentation AS4020 Interface Connections Alarm Wiring 26way High Density Male D-type. Pin Description 1 DC 3.
Setup and Test System Testing This section sets up the parameters for the system and the connection to Netspan Refer to the Netspan, document no. 605-0000-509 for the detailed configuration and set up procedures of Netspan and the AS4020 System. General The following procedures need to be carried out in order to verify the functionality and operation of all cards fitted into the Central Terminal prior to placing the AS4000/4020 system into service.
Printed Documentation AS4000 AC Setup and Test Access Concentrator: Turn-Up and DC measurements Pre-Checks Before commencing the turn-up of the rack check that the serial number and Rev levels of all card have been entered into the test form and that the SC boot chip version is recorded. DO NOT power up or plug any cards fully into their slots at this stage. Router Port Availability.
Setup and Test Place one PSU in the shelf . Switch the Rack ON by placing one breaker on. The two breakers duplicate power to each shelf and the shelves will still function if one power supply fails though the LED indicators on the power supplies will not be on. The PSU should show a green LED and one supply fail LED. Switch on the second breaker and the Red LED should extinguish. Switch off and place the second PSU in the shelf and repeat the process described in the paragraph above.
Printed Documentation 2.1V DC 2.1V 2V Access Concentrator Shelf PSU Voltages. Switch Rack off and plug in all the remaining cards in their respective positions on the shelf Repeat Test 1b for the other AC shelves if fitted.
Setup and Test Setting Up the Access Concentrator The Access Concentrator is setup using Sitespan in stand alone mode and Netspan does not need to be connected for the AC to be set up Setting the TEI and Baud Rate for Netspan Connection 1. Connect PC using AS7030 SiteStart software to the LAT port on the front of the shelf controller of the Shelf being commissioned.. 2. Set the TEI to the value designated during system planning. The TEI number must be unique to the Network managed by Netspan. 3.
Printed Documentation 3. Select the site. 4. Enter name. The name must be unique within the network or an error message is displayed and the shelf is not created. 5. Click OK to add shelf to the database. 6. The shelf is displayed on the tree view 7. Move mouse pointer to the shelf icon and right click. Select configure from the menu. 8. Continue with 'Setting up AC Rack and Shelf Configuration' below Setting up AC Rack and Shelf configuration 1.
Setup and Test Check Boot Sequence 1. SC card boots-up and displays the following LED sequence: a. Red & green LEDs both ON b. All LEDs OFF c. Green LED FLASHING d. Green LED ON e. The red LED temporarily comes ON 2. All the cards on the shelf now boot-up. 3. The TU cards display the following LED sequence: Note: The boot-up procedure for these cards takes approximately 7 minutes. a. Red LED, amber LEDs & green surface mount LEDs all ON. Green LED FLASHING b.
Printed Documentation TOP 1 Red Card failure LED, which shall be alight if the card self test fails, or if commanded by the SC. OFF 2 Green Card busy LED, to indicate live traffic is present and should not be removed.
Setup and Test 2 Green Card busy LED, to indicate live traffic is present and should not be removed. OFF Position Colour Description Status TOP 1 Red Card failure LED, which shall be alight if the card self test fails OFF SC OK Card is Active. PSU Position Colour Description Status TOP 1 Red FUSE FAIL: Illuminated if either input fuse has blown. OFF 2 Green OK Card is Active.
Printed Documentation 1. Using Sitespan create a CT rack with a dummy modem shelf. 2. From the Edit AC Shelf Properties screen assign T1-1 to the newly created CT shelf. 3. A red alarm should appear on the CTU card for the T1 activated. 4. Loopback TX to RX for the T1at the DDF. Check that the alarm clears (the amber remote alarm is lit for several seconds before clearing). 5. Reassign the CT shelf to T1-2*, T1-3, T1-4, T1-5, T1-6, T1-7 and T1-8 in turn and repeat steps 3 and 4. 6.
Setup and Test 5. On V5.1 cards, from the corresponding E1/T1, select Switch to New and then Reestablish to activate the V5.1 interface with the switch. If the V5.1 interface is not indicated as active in the XTU Card View the switch authority must be contacted . 6. On V5.2 cards from the corresponding E1/T1, select Switch to New. If the V5.2 interface is not indicated as active in the XTU Card View the switch authority must be contacted. 7. On CAS systems check alarms are clear.
Printed Documentation Access Concentrator Rack Commissioning Test Results Please photocopy test results sheet for use with each system CUSTOMER: SITE LOCATION: RACK ID: ENGINEER: DATE: 1.
Setup and Test AUX 13 AUX 14 Rack ID AC Shelf 2 Card Type PSU 1 PSU PSU 2 PSU SC SC Serial Number Rev Level AUX 1 AUX 2 AUX 3 AUX 4 AUX 5 AUX 6 AUX 7 AUX 8 AUX 9 AUX 10 AUX 11 AUX 12 AUX 13 AUX 14 Test Results Rack ID TEST # TEST LIMIT RESULT Site Inspection & Verification T1/E1 Shelf 1 103
Printed Documentation Cabling Shelf 2 System Commissioning Tests Test 1a Exchange DC Voltage Supply 1 -21.8 to -60.0V DC Exchange DC Voltage Supply 2 Test 1b Exchange DC Voltage Supply 1 -21.8 to -60.0V DC Exchange DC Voltage Supply 2 Test 2 AC Shelf 1 PSU1 5V DC 250mV 3.3V DC +0mV-300mV 2.1V DC+0mV-100mV AC Shelf 1 PSU2 5V DC 250mV 3.3V DC +0mV-300mV 2.1V DC+0mV-100mV AC Shelf 2 PSU1 5V DC 250mV 3.3V DC +0mV-300mV 2.1V DC+0mV-100mV AC Shelf 2 PSU2 5V DC 250mV 3.3V DC +0mV-300mV 2.
Setup and Test TEST #.
Printed Documentation 106
Setup and Test AS4000 CT Setup and Test Turn-Up and DC measurements Before commencing the turn-up of the rack, check that the serial number and Rev levels of all cards have been entered into the test form. Disconnect the Antenna. Rack Turn-Up and Measuring Input Voltage (Test 1a) This section describes the procedure for measuring and connecting DC to the rack, checking that the cards have the correct alarm indications on power-up and measuring the PSU output voltages.
Printed Documentation Combiner Shelf PSU.
Setup and Test Commissioning the Central Terminal Setting up Site Configuration on Netspan This procedure is used to set-up the Central Terminal for commissioning and does not require the back-haul to the Access Concentrator Site to be installed. To commission the AC Shelf the Shelf must be either connected via an RS232 interface to a Sitespan server on a Laptop PC. However the settings made during the setup process must be transferred to the NMS Netspan before it server is connected.
Printed Documentation 2. If required download the appropriate software by following the software download procedure (see Software Download) 3. Re-boot the Shelf by clicking the Reset Shelf button on the shelf controller view. Check Boot Sequence 1. SC card boots-up and displays the following LED sequence: a. Red & green LEDs both ON b. All LEDs OFF c. Green LED FLASHING d. Green LED ON e. The red LED temporarily comes ON 2. All the cards on the shelf now boot-up. 3.
Setup and Test RF Combiner Shelf Low Noise Amplifier Position Colour Description Status Top 1 Amber Power/Module Status OK ON 2 Red Power Fault OFF RF Card [RF] Position Colour Description Status Top 1 Amber Power/Module Status OK ON 2 Red Power Fault OFF Shelf Monitor Position Colour Description Status Top 1 Red Power Fault/PA Module Fault OFF 2 Amber Power/Module Status OK ON Power Amplifier[PA] Position Colour Description Status 111
Printed Documentation Top 1 Amber Power/Module Status OK ON 2 Red Power Fault/PA Module 1 Fault OFF 3 Red Power Fault/PA Module 2 Fault OFF * PA 2 is inserted inverted and the alarm indicators are also inverted Power Supply Unit [PSU] Position Colour Description Status Top 1 Amber Power OK ON 2 Red Power Fail OFF Table. RF Combiner Shelf Card LED Indications. Modem Shelf Card LEDs.
Setup and Test 3 Green Link failure Trinity 1 OFF 4 Green Link failure Trinity 2 OFF 5 Green Link failure Trinity 3 OFF 6 Green Link failure Trinity 4 OFF 7 Green Link failure Trinity 5 OFF 8 Green Link failure Trinity 6 OFF 9 Green Link failure Trinity 7 OFF 10 Green Link failure Trinity 8 OFF 11 Green Link failure Trinity 9 OFF 12 Green Link failure Trinity 10 OFF 13 Green Link failure Trinity 11 OFF 14 Green Link failure Trinity 12 OFF Position Colour De
Printed Documentation TOP 1 Red Card failure LED, which shall be alight if the card self test fails, or if commanded by the SC. OFF 2 Green OK Card is Active.. ON Position Colour Description Status TOP 1 Red Card failure LED, which shall be alight if the card self test fails OFF SC OK Card is Active. PSU Position Colour Description Status TOP 1 Red FUSE FAIL which shall be alight if either input fuse has blown. OFF 2 Green OK Card is Active.
Setup and Test Measuring Central Terminal TX Power The recommended single user TX output power is +18dBm for 3.4-3.6GHz, +20dBm for 1.81.9GHz, and +21dBm for all other bands. This procedure is used to measure the TX output power when set up for 3 Users. Note: If proceeding to commissioning the DACU should be powered up and allowed to warm up for 30 mins prior to setting the RX sensitivity.. This procedure is for setting up AS4000 shelves only. Tools and equipment needed.
Printed Documentation Figure Power Level measurement Test Set-Up Measure the output of shelf 1. (This test is repeated for other installed shelves) 1. Remove the RF cards for all but the shelf being commissioned 2. Connect Sitespan to the shelf under test. See Connection to Sitespan 3. Open The DTU Card View and click the Commission Button. This button places the shelf into an internal commissioning test mode. This button is clicked before the commissioning procedure is started.
Setup and Test 4. Open the DTU card properties. Set any 4RWs to OOS160k and the remainder to OOS (These can be selected from the by clicking the mouse on the state to cycle through the options).
Printed Documentation 5. View the Modem Shelf Properties using Sitespan. Set the TX and RX gain to 0(zero) 6. Ensure that a 30dB attenuator is connected to the power sensor if required to protect the sensor. 7. Calibrate/set-up power meter according to manufacturers instructions. 8. Connect the power sensor at the top of the rack as per diagram 9. Measure O/P power and ensure the level is less than -20dBm 10. Adjust TX Gain for the band of the system under test. Start with the TX gain set to 3300.
Setup and Test 2.0-2.3GHz +27dBm 2.3-2.5GHz +27dBm 3.4-3.6GHz +24dBm 11. Set RW1 to OOS(160K) and all other RWs OOS 12. Measure the output power: ensure the level is as in the table below Band Reading ±1dB 1.8-1.9GHz +20dBm 2.0-2.3GHz +21dBm 2.3-2.5GHz +21dBm 3.4-3.6GHz +18dBm 13. Repeat power reading for single RW OOS(160k), for all other individual RWs 14. Record the result (see Test Results) 15.
Printed Documentation Procedure in case of card boot-up failure Procedure in case of card boot-up failure If the cards inserted into the shelf do not boot-up, the top red LED on the card will be either continuously ON or FLASHING. The following steps should be followed: 1. Check cards are properly inserted into the shelf, in the correct positions 2. Reset the SC card using Netspan/Sitespan, under the card view. 3. The cards boot-up.
Setup and Test Setting RX sensitivity using DACU 2.0-2.3GHz & 3.4-3.6GHz Band (Test 6) If a DACU is not available use Setting RX Sensitivity without DACU Preparation for commissioning at the Central Terminal 1. The DACU should be powered up and allowed to warm up for 30 mins to achieve stability prior to setting the RX sensitivity. For details on setting up the DACU see Connecting the DACU 2. Enter the loss values in the DACU calibration chart for the relevant frequency See chart below. 3.
Printed Documentation 14. Record results in test results sheet 15. Power off the DACU. 16. Put all RWs back in service. Restoring shelf connections 1. Remove the test equipment and connecting cables. 2. Replace the Shelf covers and the protective cap on the coupler. 3. Do not remove the Sitespan connection at this time.
Setup and Test Setting RX Sensitivity without DACU Tools and equipment needed.
Printed Documentation Test Set-up 2. Measure and calibrate the loss of all components as per diagram above: 3. Measure (1)A-B, (2)B-C, (3)C-D and (7)D-E. 4. Enter values in calibration chart for the relevant frequency. 5. Calculate/determine overall path loss and required ST output power and hence required power meter reading. 6. Connect cables as per diagram above. 7. Ensure that the commissioning button is off.
Setup and Test BER Test The BER test is best done from the network management centre but if a management centre backhaul has not yet been established the test may be performed at the AC site and should be set up by connecting Local Netspan/Sitespan to AC Rack, building site locally and create subscriber. Setting up system tests at the Access Concentrator. Create CAS XTU in a spare slot (slot 10 if spare). Create CAS subscriber in Sitespan. Note the timeslot and E1 link used.
Printed Documentation The presence of the loopback should be seen at the BER test set. Inject 1 error into the test signal and observe it on the incoming signal to check that errors are detected. Start and stop the test to clear the injected error. Observe the return signal on the T1/E1 out to establish that the link is error free. Run BER test for 1 Hour. On completion of the test remove the loopback (open the Edit DA ST window and click the Loopback box to remove the tick and click OK.
Setup and Test Setting the System into Service Checking alarms and connections to Netspan At the AC Test the RS232 disconnect alarm by disconnecting the adapter on Sitespan port I. Pull card and check alarm is visible at NMC. At the NMC set the free list entries.
Printed Documentation AS4020 CT Setup and Test AS4020 Menu Map The system parameters are set from the front panel of the AS4020 The chart below shows the menu layout 128
Setup and Test 129
Printed Documentation AS4020 error messages The List below shows error message codes that are reported to the front panel of the AS4020 Code 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Meaning the image being loaded has a magic number that identifies it, this number has been corrupted. the image has a build information header, (not the Airspan file header), attached containing which has an associated checksum, this is corrupted.
Setup and Test Set Traffic/Management Ports The traffic port connects to the Ethernet connecting to the internet service provider and the management port connects to the Netspan server. Enter the following parameters from the front panel of the AS4020. The values are determined by the server that the network is connected to. IP address = in the form xxx.xxx.xxx.xxx i.e 192.254.130.030 Subnet mask = in the form xxx.xxx.xxx.xxx i.e 255.255.000.
Printed Documentation Set NMS Menu Management Port Num Port Number used to connect to Netspan Admin Password Password protection for the AS4020. When set only authorised persons can make changes to the AS4020 configuration. If changes are made Via Sitespan a password is requested if set. If no password is set Netspan still requests a password but any entry will be successful in allowing access to the configuration.
Setup and Test Set TX Power The recommended single user TX output power (QPSK/16QAM) is +18dBm for 3.4-3.6GHz, +20dBm for 1.8-1.9GHz, and +21dBm for all other bands. This procedure is used to measure the TX output power when set up in commissioning mode 1. System Soak It is necessary that the system is powered up for at least two hours to allow for temperature stabilisation before proceeding with the measurement of the TX power Tools and equipment needed.
Printed Documentation Uplink Frequency Channel Bandwidth PN Code RF Commissioning Card Type RX Sensitivity TX Power Enter UL frequency kHz with leading 0 e.g 03522651 00002 (=3MHz) PN code as supplied** Mode 1 Note: If in commissioning mode the top menu displays RF commissioning alarm enter card type ( See number on RF card) 02500 03000 ** The commissioning procedure described in this document is not restricted to any particular RF channel or PN code.
Setup and Test RF Card Cross Reference Chart RF Card Part Number 605-0010-296 605-0010-092 605-0010-093 605-0010-102 605-0010-103 605-0010-237 605-0010-238 605-0010-294 605-0010-322 605-0010-073 605-0010-074 605-0010-069 605-0010-070 605-0010-077 605-0010-078 605-0010-081 605-0010-082 605-0010-075 605-0010-076 605-0010-071 605-0010-072 605-0010-079 605-0010-080 605-0010-352 605-0010-083 605-0010-084 605-0010-163 605-0010-122 605-0010-295 605-0010-330 605-0010-394 605-0010-396 605-0010-399 AS4020 Card Type
Printed Documentation Go to Top Menu >Setup Menu >RF Menu>TX Power TX power To set the CT to transmit at QPSK or 16QAM adjust the TX Power until the output of the transmitter by increasing or decreasing the value until the level tabulated below is reached. If the CT is required to operate with a downlink of 64QAM then the output should be backed off by 3dB. Note: This will affect the system coverage and should be taken into account at the radio planning stage.
Setup and Test Set RX sensitivity using a DACU without Calibrated Coupler This procedure should be used to commission the CT if using a DACU. At the end of this test a label with the calibrated value should be attached to the coupler. Calibrated attenuators and cables are provided with the DACU for this test. The RX sensitivity is set according to the required CT RX level. It is important to note that the lower the modulation rate the further the geographical spread.
Printed Documentation 3. Calculate/determine total path loss and required DACU output power and hence power meter reading. 4. Connect cables and equipment as per diagram below using 30+30+20dB calibrated attenuators. If coupler calibration known set up as in step 9 and go to step 6 5. Zero power meter. Calibrate and apply measurement offset for operational frequency if applicable. 6. On the AS4020 go to Top Menu >Setup Menu >RF Menu>RX Sensitivity. Set RX to 2500 7.
Setup and Test c d e attenuators Power meter reading with coupler Difference between readings Coupler loss if [c] is greater than [b] then subtract [d] from [a] if [c] is less than [b] then add [d] to [a] Table 2 11. Populate the table below with values obtained from calibrated components and planned levels to calculate/determine overall path loss and required ST output power and hence required power meter reading. RF Channel No: RF Section Cable Loss(1) Coupler loss loss.
Printed Documentation enabled does not mean that the equalizer is disabled but that the training of the equaliser is finished.) Check that the equalizer converges OK. 2. From the ST LAT type TE1 to exit commissioning mode 3. From the AS4020 front panel exit commissioning mode by selecting RF Commissioning = Off.
Setup and Test Connecting the DACU The following cables are provided with the DACU. Description DC Power Cord Qty 1 AC Supply Cable PC Laptop Cable IF Link Cable 1 Hexagonal Key Laminated Kitting / Connection sheet 1 1 1 Airspan DACU Kitting List Comment Connects the dc power supply from the red and black 4mm sockets on the DACU, labelled “+” and “-“ to either the IDU dc power jack, labelled “12V ---- 1.
Printed Documentation Fit the RF Module The RF module is inserted into the compartment on the right of the DACU. it is secured using two hexagonal headed screws.
Setup and Test Attenuator (30dB), 5W Adaptor (N to SMA) SMA Torque spanner Termination (50 Ohm) Laminated Kitting / Calibration sheet (front) Laminated Pro-forma worksheet (on reverse of above) Marker Pen 2 Second and third in line from combiner 1 Needed to connect N-type pads to 4m cable 1 To tighten SMA's 1 Terminates an unused power meter port 1 A sheet showing a labelled photograph of all the RF Module Kit items, underneath which there is a table to fill out all the calibration details.
Printed Documentation Set RX Sensitivity without a DACU Tools and equipment needed.
Setup and Test For networks where co or adjacent frequencies are reused to provide cellular type network coverage with limited available spectrum (ie.
Printed Documentation turn between the TX output and the power meter and measure the loss added as the component is inserted. Measure (1)A-B, (2)B-C, (3)C-D and (7)D-E. 7. Calculate and enter values in calibration chart for the relevant frequency. RF Channel No: Ref TX output RF Section A-B Atten.(1) B-C Atten.(2) C-D Atten.(3) Sub Total (4) 1+2+3 Required CT RX Level (5) see table 1 ST TX Power (6)=4+5 RF Section D-E Atten (7) Power Meter (8) = 6-7 8.
Setup and Test 11. From the AS4020 front panel exit commissioning mode by selecting RF Commissioning = Off.
Printed Documentation Packet System Testing Data Tests To pass Ethernet traffic through the AS4020 system, it will be necessary to transfer data between a Server connected to the “Traffic” Ethernet port of the AS4020 CT, and a PC connected to an ST. To test basic functionality, the following throughput speed tests are performed. Test Method & Results: Windows 2000 has a built-in FTP server.
Setup and Test Configuration of the FTP Server: The FTP Server needs a home directory – this is where the “root” of the FTP server will be located, and where the files will be downloaded from. These steps detail configuring the directory location, and additionally some other required parameters such as access rights: 1. Right-Click on the “My Computer” icon on the desktop, and choose the option “Manage”.
Printed Documentation Creating suitable download / upload test files: Due to the high transfer rates possible with the AS4020 system, suitably sized test files should be transferred. The recommended test file sizes are of the order of 1Mbyte (uploading) and 10Mbyte (downloading). We must also ensure that any file compression does not result in files appearing to be transferred faster than they actually are.
Setup and Test Using the FTP Client, and automating the transfers: To perform the data transfers, an FTP Client running on a PC connected to an ST will download and upload data files to the FTP Server running on a computer connected to the same network as the Traffic Port of the AS4020. To avoid the influence of other network traffic, all other computers on the network should be disconnected.
Printed Documentation 6. The Server will ask for a username and password. Enter the username “ftp”, and the password can be anything, even left blank if the FTP Server is set up as described earlier. Note: A blank anonymous password will not work on all types of FTP server, some may require a correctly formatted email address (e.g. a@b.com) as the password. Also, the username ftp is equivalent to typing the username anonymous. 7. Switch the transfer mode to binary, by entering the command bin; 8.
Setup and Test Please refer to the technical note at the end of this section, explaining why the figure will be less than the theoretical maximum data rate available. 10. To exit from the FTP program, type “quit” at the prompt Creating batch files for automatic File Transfers: As mentioned earlier, it will be much more convenient to have test batch files which will automatically perform a file transfer, and then pause to show the results.
Printed Documentation Therefore the “Ethernet” overhead is 100*1514/1460 = 3.7% Additionally, there is an overhead associated with Airspan’s air interface. The data is sent in small blocks, transmitted every 4ms on multiple RW channels simultaneously. Additionally, an ST can receive up to 4 blocks simultaneously. Each block has a 4 byte overhead.
Setup and Test Voice Option Testing Option Module Test It is only possible to fully test the voice module if the installation of the AC and the backhaul connections to the switch are in place. Netspan also needs to be connected. The card is set for 120ohm or 75ohm dependant on the type of backhaul selected on Netspan. When connected to the AC using the correct impedance port the relevant LED should be green. A red LED signifies link disconnection, and an amber LED signifies link present but faulty.
Printed Documentation Central Terminal Rack Commissioning Test Results Please photocopy test results sheet for use with each system CUSTOMER: SITE LOCATION: RACK ID: ENGINEER: DATE: Test Equipment Calibration 1.
Setup and Test Note: The cable supplied with each DACU is calibrated for a range of frequencies. If a cable other than the original cable is used then an adjustment to the DACU output power to 98dB at the receiver must be made. i.e.
Printed Documentation PSU3 Modem Shelves AS4020 shelf 1 AS4020 shelf 2 AS4020 shelf 3 AS4020 shelf 4 Rack ID TEST # TEST LIMIT Site Inspection & Verification T1/E1Cabling Modem Shelf 1 Modem Shelf 2 Modem Shelf 3 Modem Shelf 4 System Commissioning Tests Test 1a Exchange DC Voltage CT Rack Supply 1 -36.0 to 60.0V DC CT Rack Supply 1 Extn Rack Supply 1 Extn Rack Supply 2 Test 1b Exchange DC Voltage CT Rack Supply 1 -36.0 to 60.
Setup and Test 159
Printed Documentation AS4000- ACCESS CONCENTRATOR ACCEPTANCE FORM CONTRACT OR CUSTOMER'S REF. NO: AIRSPAN NETWORKS REF. NO: SITE IDENTITY: The Customer accepts that the following equipment has been supplied, installed and tested.
Setup and Test Customer Representative Name:__________________________ Position:________________________________ Date:___________________________ Signature:______________________________ Airspan Representative Name:__________________________ Position:________________________________ Date:___________________________ Signature:______________________________ CUSTOMER COPY 161
General Customer Material Repair and Return Procedures Introduction This document describes the procedures, responsibilities, and terms and conditions for the repair and replacement services offered by Airspan Communications Limited (Airspan) to its customers and approved contractors. It shall apply only to Field Replaceable Units (FRUs) manufactured or supplied by Airspan Communications Limited.
Printed Documentation The customer bears the risk associated with any FRU returned for repair or replacement until Airspan receives the item. The customer bears the cost of delivery of the FRU for repair Airspan bears the risk associated with the return of a repaired FRU or replacement until the customer has taken delivery of it. The title for any repaired or replaced unit passes to the customer on delivery, providing that the appropriate payment has been made to Airspan.
General Normal Repair Out-of-warranty a. The warranty period for a FRU repaired or replaced out of warranty shall be ninety (90) days from the date of shipment of the item by Airspan to the customer. Repair and Return Procedure The normal process is for the customer to obtain a Return Material Authorisation (RMA) number, and then return the suspect faulty item to Airspan for repair. Airspan will repair the FRU, or replace it if appropriate, and return it to the customer.
Printed Documentation 166
General Action Taken by Customer Requesting a Repair Return Whenever a customer has a query, or determines that they have a suspect faulty FRU that they wish to return, they should take the following action: a. Contact either the local Airspan office or the 24-hour Airspan International Call Centre.
Printed Documentation Tel:+44 1895 467 467 During UK working hours, the Customer Service Help Desk can be contacted at: Tel:+44 1895 467 239 Fax:+44 1895 467 472 Unless instructed otherwise, customers should ship the return item to the following address: Customer Service Airspan Communications Ltd Airspan House Cambridge House Oxford Rd Uxbridge Middlesex UB8 1UN England The local Airspan Account Team will provide details of any alternative local office contact numbers and addresses.
General In-Warranty Advance Replacement If a FRU is under warranty, and is critical to the customer’s system, Airspan will despatch a suitable replacement, if available, from the rotapool in advance of receiving the suspect item. Airspan will ship the replacement item from the nearest location holding rotapool stock of that item. Out of Warranty Advance Replacement If an FRU is no longer under warranty, as defined above, the customer may request an advance replacement item.
Printed Documentation Repair Charges In Warranty Charges Providing the "in-warranty" conditions are met, Airspan will carry out all repairs or replacements free of charge. Out of Warranty Charges For FRUs that are out of warranty, repairs shall be carried out at the standard rate for that item, as listed in the Repair Price Schedule. Airspan will provide prices on application for FRUs not listed in the Repair Price Schedule.
General Warranty on Repaired Items Normal Repair In-warranty The warranty for an item repaired or replaced in warranty shall be 90 days or the remainder of the original outstanding warranty period for the returned item, whichever is the greater. Normal Repair Out-of-warranty The warranty for an item repaired or replaced out of warranty shall be 90 days from delivery of the item to the customer. Return & Repair Tag Airspan provides a tag to be attached to each item being returned.
Printed Documentation 172
General Defective Equipment Information Form RMA Number (provided by Airspan) Card/Assembly Description Part Number and Revision (if Applicable) Serial Number Date Commissioned Date Fault Reported Location of Assembly in CT Rack Shelf Location of Subscriber Terminal SUBSCRIBER TERMINAL INFORMATION Power Supply Type (e.g.
Printed Documentation Circuit Board Assemblies Circuit board assemblies must be individually boxed in Airspan-approved shipping containers, to properly protect them from static electricity damage. Static Control Rules Airspan uses state-of-the-art semiconductors to obtain the fastest, most reliable operation. These components are highly sensitive, and can be damaged by a static discharge as low as 250V.
General Individually boxed PCBs must be placed into a larger packing case for shipment. Board boxes alone do not sufficiently protect against shipping damage. Empty space in shipping cases must be filled with additional shipping boxes to prevent part movement and damage during handling. Power Supplies And Peripherals Each type of assembly must be shipped in its specifically-designed packing box. Retain individual shipping containers for these items.
Printed Documentation Specifications Central Terminal The following tables provide technical specifications for the Central Terminal. PHYSICAL CHARACTERISTICS CT Rack Dimensions, (without brackets): Full Height Compact Width 600mm 600mm Height 2175mm 1500mm Depth 300mm 300mm Shipping Weight: Rack Frame 60 kg Air Inlets/Outlets 16.5 kg Combiner Shelf 30 kg Power Amp 4.5 kg (each) LNA 1 kg Frequency Dependant TX filter 1 kg Frequency Dependant PSU 1.5 kg (each) AS4020 Shelf 3.
General Storage Humidity, non-condensing Less than 100% Air Pressure 70 kPa 106 kPa POWER REQUIREMENTS DC Input Voltage Operating Range. (N.B. This supply to be a guaranteed SELV from an EN60950 approved source.) Maximum Range, -36.0V DC to 60.0V DC @ 540W DC Input Current (Fully populated CT Rack) 11.5 Amps max. @ -48V DC 9 Amps max. @ -60V DC Recommended Power Distribution Fusing (With a readily accessible disconnect device which will isolate all poles.) -36.
Printed Documentation Copyright Information Airspan Networks Inc 2003 This manual is subject to revision. All rights reserved. Right of modification reserved. This manual is supplied without liability for errors or omissions. No part of this manual may be reproduced or used except as authorised by contract or other written permission. 7.
General Contact Information UK Office for sales and general enquiries Airspan Communications Ltd Cambridge House Oxford Road Uxbridge Middlesex UB8 1UN Call +44 (0) 1895 467100 Fax +44 (0) 1895 467101 email sales@ airspan.com Internet: Airspan.com Customer Service Help-Desk for customer service emergency Airspan Communications Limited Cambridge House Oxford Road Uxbridge Middlesex UB8 1UN Int. Tel: +44 (0) 1895 467 467 Int. Fax: +44 (0) 1895 467 472 E-mail: Support@Airspan.
Printed Documentation Problems with this Guide If you encounter any problems or difficulty using this guide. Please Contact: Malcolm Windett The Documentation Manager Airspan Communications Ltd Cambridge House Oxford Road Uxbridge Middlesex UB8 1UN Call +44 (0) 1895 467185 Fax +44 (0) 1895 467182 email mwindett@ airspan.
General Document Purpose General Purpose of Document This document describes the installation and commissioning of the Airspan AS4020 Central Terminal (CT) Racks and associated shelves to Release 7.21 specifications. Prerequisite skills Personnel installing and commissioning Airspan products must have a basic knowledge of telephony and radio communications, and have experience in installing telecommunications products.
Printed Documentation Warnings and Cautions SAFETY 1. Read and follow all warning notices and instructions marked on the product or included in this manual 2. Do not allow anything to rest on the power cord and do not locate the product where persons could step or walk on the power cord. 3. When installed in the final configuration, the product must comply with the applicable Safety Standards and regulatory requirements of the country in which it is installed.
General Concentrator AS4000 R series SIU Responsible party for compliance is: Charles Blackham, Airspan Networks Inc.,Cambridge House, Oxford Rd, Uxbridge, Middlesex, England, UB8 1UN. Telephone (44) 1 895 467450. CAUTION: European Directive 1999/519/EC details basic restrictions and reference levels on human exposure to electromagnetic fields as advised by the ICNIRP.
Printed Documentation Issue Status Issue Rev A Rev B Rev C Rev D Rev E Rev F Rev G 184 Date December-2002 July 2003 September-2003 September-2003 October 2003 January 2004 January 2004 Notes Release 7.10 Release 7.11 Release 7.20 Release 7.20 changes to DACU. Release 7.21 Release 7.22 Release 7.
Glossary A A/D: Analogue/Digital AC: Access Concentrator ADPCM: Adaptive Differential Pulse Code Modulation AGC: Automatic Gain Control AIS: Alarm Indication Signal or All Ones AMI: Alternate Mark Inversion AU: Analogue Unit B BER: BIT Error Rate C CAS: Channel Associated Signalling CPE: Customer Premises Equipment CT: Central Terminal CTU: Concentrated Tributary Unit CU: Compression Unit D D/A: Digital/Analogue DA: Demand Assignment DACU: Demand Assignment Commissioning Unit DC: Direct Current DIP: Dip
Printed Documentation I/0: Input/Output IP: Internet Protocol IS: In Service ISDN: Integrated Services Digital Network ITU-T: International Telecommunications Union -Telecommunications L LAT: Local Access Terminal LED: Light Emitting Diode LNA: Low Noise Amplifier M MF: Multi-Frequency MODEM: Modulator/Demodulator MON: Monitor MSTP: Modem Shelf Termination Panel MU: Modem Unit N NTU: Network Termination Unit NVRAM: Non Volatile Random Access Memory O OOS: Out of Service P PA: Power Amplifier PROM: Pro
Glossary STP: Shelf Termination Panel T TCP: Transmission Control Protocol TEI: Terminal Equipment Identifier TU: Tributary Unit TU8: Tributary Unit Eight E1 ports TX: Transmit U UCP: Uplink Code Phase V VDU: Video Display Unit VF: Voice Frequency X XTU: Exchange Tributary Unit 187
Index A AS4000 Racks ........................................1 C Cable Trays.............................................4 Commissioning Access Concentrator Rack ..........................................................97 Commissioning Central Terminal Rack ..97 Commissioning Process ........................97 D DC Power .............................................16 Delivery Inspection..................................4 F Flooring...................................................