Specifications
PRODUCT SPECIFICATIONS Split System Air Conditioner: R4A4
6 421 65 6240 06
Specifications subject to change without notice.
EXPANDED COOLING PERFORMANCE RATINGS For Outdoor / Indoor Models #
For complete ratings information, use the AHRI website directory search: www.AHRIdirectory .org.
New ratings may be listed online before Specification Sheets are updated.
EVAPORA-
TOR AIR
CONDENSER ENTERING AIR TEMPERATURES °F(°C)
75 (23.9) 85 (29.4) 95 (35) 105 (40.6) 115 (46.1) 125 (51.7)
CFM
EWB
°F
Capacity
MBtuh
Total
Systm
KW**
Capacity
MBtuh
Total
Systm
KW**
Capacity
MBtuh
Total
Systm
KW**
Capacity
MBtuh
Total
Systm
KW**
Capacity
MBtuh
Total
Systm
KW**
Capacity
MBtuh
Total
Systm
KW**
Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
018 Size Outdoor Section With EA*4X19L17A* Indoor Cooling
525
72 20.84 11.15 1.18 20.08 10.86 1.33 19.26 10.56 1.49 18.34 10.22 1.67 17.28 9.84 1.89 16.07 9.40 2.13
67 19.05 13.80 1.19 18.30 13.49 1.34 17.50 13.16 1.50 16.60 12.80 1.68 15.58 12.39 1.89 14.40 11.93 2.13
63{{ 17.78 13.32 1.20 17.04 12.99 1.34 16.24 12.64 1.50 15.35 12.25 1.68 14.35 11.82 1.89 13.21 11.33 2.14
62 17.42 16.39 1.20 16.70 16.06 1.34 15.92 15.68 1.50 15.12 15.12 1.68 14.34 14.34 1.89 13.45 13.45 2.13
57 17.00 17.00 1.20 16.41 16.41 1.34 15.79 15.79 1.50 15.10 15.10 1.68 14.32 14.32 1.89 13.43 13.43 2.13
600
72 21.18 11.76 1.21 20.40 11.48 1.35 19.56 11.17 1.52 18.61 10.83 1.70 17.52 10.45 1.92 16.27 10.01 2.16
67 19.36 14.78 1.22 18.61 14.48 1.36 17.78 14.15 1.52 16.86 13.79 1.71 15.81 13.37 1.92 14.62 12.90 2.16
63{{ 18.10 14.24 1.23 17.35 13.91 1.37 16.53 13.56 1.53 15.62 13.17 1.71 14.59 12.73 1.92 13.42 12.24 2.16
62 17.79 17.69 1.23 17.14 17.14 1.37 16.49 16.49 1.53 15.76 15.76 1.71 14.94 14.94 1.92 14.00 14.00 2.16
57 17.72 17.72 1.23 17.11 17.1 1 1.37 16.46 16.46 1.53 15.74 15.74 1.71 14.92 14.92 1.92 13.98 13.98 2.16
675
72 21.42 12.36 1.23 20.63 12.08 1.38 19.76 11.77 1.55 18.80 11.43 1.73 17.69 11.05 1.94 16.41 10.61 2.19
67 19.60 15.75 1.25 18.83 15.44 1.39 17.99 15.11 1.55 17.05 14.75 1.73 15.99 14.33 1.95 14.77 13.85 2.19
63{{ 18.34 15.14 1.26 17.57 14.81 1.40 16.74 14.45 1.56 15.82 14.06 1.74 14.77 13.61 1.95 13.59 13.10 2.19
62 18.33 18.33 1.25 17.71 17.71 1.40 17.04 17.04 1.55 16.28 16.28 1.74 15.43 15.43 1.95 14.46 14.46 2.19
57 18.31 18.31 1.25 17.68 17.68 1.40 17.01 17.01 1.55 16.26 16.26 1.74 15.41 15.41 1.95 14.44 14.44 2.19
EVAPORA-
TOR AIR
CONDENSER ENTERING AIR TEMPERATURES °F(°C)
75 (23.9) 85 (29.4) 95 (35) 105 (40.6) 115 (46.1) 125 (51.7)
CFM
EWB
°F
Capacity
MBtuh
Total
Systm
KW**
Capacity
MBtuh
Total
Systm
KW**
Capacity
MBtuh
Total
Systm
KW**
Capacity
MBtuh
Total
Systm
KW**
Capacity
MBtuh
Total
Systm
KW**
Capacity
MBtuh
Total
Systm
KW**
Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
024 Size Outdoor Section With EA*4X25L17A* Indoor Cooling
700
72 27.81 14.89 1.62 26.74 14.49 1.80 25.61 14.07 2.00 24.39 13.62 2.23 23.06 13.14 2.51 21.56 12.60 2.83
67 25.46 18.45 1.62 24.46 18.04 1.80 23.40 17.61 2.00 22.25 17.13 2.23 21.01 16.63 2.51 19.58 16.06 2.83
63{{ 23.79 17.82 1.62 22.84 17.40 1.80 21.83 16.94 2.00 20.74 16.47 2.24 19.53 15.94 2.52 18.16 15.36 2.85
62 23.31 21.92 1.62 22.38 21.48 1.80 21.40 21.01 2.00 20.37 20.37 2.24 19.43 19.43 2.51 18.33 18.33 2.84
57 22.74 22.74 1.62 22.00 22.00 1.80 21.20 21.20 2.00 20.34 20.34 2.24 19.39 19.39 2.51 18.30 18.30 2.84
800
72 28.26 15.70 1.66 27.15 15.30 1.84 25.97 14.87 2.04 24.70 14.42 2.27 23.33 13.94 2.54 21.80 13.40 2.87
67 25.87 19.75 1.66 24.84 19.33 1.84 23.75 18.90 2.04 22.56 18.42 2.27 21.27 17.91 2.55 19.81 17.34 2.87
63{{ 24.22 19.04 1.66 23.25 18.61 1.84 22.19 18.15 2.04 21.05 17.67 2.28 19.82 17.14 2.55 18.40 16.54 2.88
62 23.79 23.64 1.66 22.94 22.94 1.84 22.09 22.09 2.04 21.17 21.17 2.27 20.16 20.16 2.55 19.00 19.00 2.87
57 23.69 23.69 1.66 22.90 22.90 1.84 22.06 22.06 2.04 21.14 21.14 2.27 20.13 20.13 2.55 18.98 18.98 2.87
900
72 28.57 16.50 1.70 27.42 16.10 1.87 26.21 15.67 2.08 24.91 15.21 2.31 23.51 14.73 2.58 21.94 14.19 2.90
67 26.18 21.03 1.70 25.11 20.60 1.88 23.99 20.16 2.08 22.77 19.68 2.31 21.46 19.16 2.58 19.98 18.58 2.91
63{{ 24.53 20.22 1.70 23.52 19.79 1.88 22.44 19.33 2.08 21.28 18.83 2.32 20.02 18.30 2.59 18.58 17.68 2.92
62 24.50 24.50 1.70 23.67 23.67 1.88 22.78 22.78 2.08 21.82 21.82 2.31 20.76 20.76 2.59 19.55 19.55 2.91
57 24.47 24.47 1.70 23.64 23.64 1.88 22.75 22.75 2.08 21.79 21.79 2.31 20.73 20.73 2.59 19.52 19.52 2.91
} Sensible capacities shown are based on 80_F(27_C) entering air at the indoor coil. For sensible capacities at other than 80_F(27_C ) , deduct 835 Btuh (245 kW) per
1000 CFM (480 L/S) of indoor coil air for each degree below 80_F(27_C), or add 835 Btuh
(245 kW) per 1000 CFM (480 L / S ) of indoor coil air per degree above 80_F(27_C).
# Expanded cooling capacities are based on indoor and outdoor unit at the same elevation per AHRI standard 210/240 - 2008. If additional tubing length and/or indoor
unit is located above outdoor unit, a slight variation in capacity may occur.
** System kw is total of indoor and ou tdoor unit kilowatts.
{{ At TVA rating indoor condition (75_ F edb/63_F ewb). All other indoor air temperatures are at 80_F edb.
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
EWB — E ntering Wet Bul b