Installation Instructions
GENERAL
M Series
Manufactured Housing Evaporator Coils
IM-MHC-0666880-06
August 2018
Installation Instructions
ADP evaporator coils are designed for use with condensing units or heat pump units. These
instructions are intended as a general guide and do not supersede local codes in any way.
Consult with local authorities having jurisdiction before installation. Installer must comply
with all local, state, and federal codes and regulations during installation. Read this
installation manual and all “Warning” statements prior to installing.
ADP manufactured housing evaporator coils are designed for pull-through configuration
with use with many manufactured housing electric furnaces (down-flow and upflow) and gas
furnaces (down-flow). ADP offers a selection of other products for other applications.
Check coil for shipping damage and verify the contents of the box containing the evaporator
coil. If you should find damage, immediately contact the last carrier. Verify the efficiency or
performance requirements, such as SEER, EER, and/or HSPF, are appropriate with the
matched condensing or heat pump units. See AHRI ratings
directory for more information. Check outdoor unit
manufacturer for proper line sizing. Coils are shipped with a
10 psi dry air holding charge. Puncture rubber plug on
suction line to release charge before removing plugs. The
absence of pressure does not verify a leak. Check the coil for
leaks before installing or returning it to your wholesaler.
Drain Pans
Drain pans are made of a polymer that can withstand
temperatures up to 400 deg. F.
Maintain a 3" clearance on drum type heat
exchangers and 1½" on sectionalized heat
exchangers.
Coil should be level, or pitched slightly toward the drain
connection.
Airflow
Airflow face velocity above 350 ft/min is not
recommended for downflow applications due to
potential water blow-off.
Low airflow below 360 CFM per 12,000 BTUH can lead
to coil freeze-up problems.
Improper airflow across the evaporator coil can cause
component or system problems.
2175 West Park Place Blvd., Stone Mountain, GA 30087
www.adpnow.com
Product improvement is a continuous process at Advanced Distributor Products. Therefore, product specifications are subject to change without notice and
without obligation on our part. Please contact your ADP representative or distributor to verify details.
© by Advanced Distributor Products. All rights reserved.
SAFETY CONSIDERATIONS
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and
on your appliance. Always read and obey all safety messages.
This is the safety alert symbol.
This symbol alerts you to potential hazards that can kill or hurt
you and others.
All safety messages will follow the safety alert symbol and
signal word. These signals words mean the following:
DANGER: You can be killed or seriously injured if you don’t
immediately follow instructions.
WARNING: Indicate a potentially hazardous situation which, if not
avoided, could result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not
avoided, may result in minor or moderate injury. Caution may also
be used to alert against unsafe practices.
NOTICE: Indicates a statement of company policy as the message
relates directly or indirectly to the safety of personnel or protection of
property.
IMPORTANT: More detailed information concerning the statement of
company policy as the message relates directly or indirectly to the
safety of personnel or protection of property.
All safety messages will tell you what the potential hazard is, tell you how
to reduce the chance of injury, and tell you what can happen if the
instructions are not followed.