Specification Sheet
26
518 71 2005 06
Specificatio ns subject to change without notice.
ELECTRICAL DATA (CONT)
MODEL
NOMINAL
V-PH- HZ
VOLTAGE
RANGE
COMPRES -
SOR
OFM IFM
NOMINAL
ELECTRIC
HEAT
POWER SUPPLY
MIN MAX RLA LRA FLA FLA kW FLA MCA MOCP
60
208/230- 1- 60 197 253 24.4 144.2 1.3 7.7
-/- -/- 39.5 60
3.8/5 18.1/20.8 62.1/65.5 70/70
5.4/7.2 25.9/30 71.9/77 80/80
7.5/10 36.1/41.7 84.6/91.6 90/100
11.3/15 54.2/62.5 107.3/117.6 110/125
15/20 72.2/83.3 129.8/143.6 150/150
208/230- 3- 60 197 253 16 110 1 7.6
-/- -/- 28.7 40
3.8/5 10.4/12 41.7/43.7 45/45
7.5/10 20.8/24.1 54.7/58.8 60/60
11.3/15 31.2/36.1 67.7/73.8 70/80
15/20 41.4/47.9 80.4/88.5 90/90
460-3-60 414 506 7.8 52 0.5 4
-/- -/- 14.3 20
10 12/12 29.3/29.3 30/30
15 18/18 36.8/36.8 40/40
20 24.1/24.1 44.4/44.4 45/45
See Legend and Notes.
LEGEND
FLA - Full Load Amps
IFM - Indoor Fan Motor
LRA -Locked Rotor Amps
MCA - Minimum Circuit Amps
MOCP - Maximum Over Current Protection
OFM - Outdoor Fan Motor
RLA - Rated Load Amps
A09604