Specifications
PRODUCT SPECIFICATIONS Split System Heat Pump: N4H6
428 71 6270 01 14
Specifications subject to change wi thout notice.
HEAT PUMP HEATING PERFORMANCE CONTINUED
INDOOR AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES ° F (° C)
- 3 ( - 19.4) 7 (- 13.9) 17 ( - 8.3) 27 (- 2.8) 37 (2.8) 47 (8.3) 57 (13.9) 67 (19.4)
EDB
°F (°C)
CFM
Capacity MBtuh
Tota l
Sys
KW†
Capacity MBtuh
Tota l
Sys
KW†
Capacity MBtuh
Tota l
Sys
KW†
Capacity MBtuh
Tota l
Sys
KW†
Capacity MBtuh
Tota l
Sys
KW†
Capacity MBtuh
Tota l
Sys
KW†
Capacity MBtuh
Tota l
Sys
KW†
Capacity MBtuh
Tota l
Sys
KW†
Tota l Integ* To t a l Integ* To t a l Integ* Tota l Integ* To t a l Integ* To t a l Integ* Tota l Integ* Tota l Integ*
60 Size Outdoor Section With FVM4X60***L Indoor Section - HI
65
(18.3)
1500 23.79 21.88 3.26 29.29 26.92 3.46 36.45 33.23 3.72 42.81 38.02 3.97 50.01 45.51 4.27 57.93 57.93 4.63 66.85 66.85 4.98 75.37 75.37 5.43
1625 24.02 22.09 3.27 29.54 27.14 3.46 36.69 33.45 3.71 43.07 38.25 3.95 50.33 45.80 4.24 58.31 58.31 4.58 67.16 67.16 4.91 75.53 75.53 5.33
1750 24.26 22.32 3.28 29.79 27.38 3.47 36.89 33.63 3.70 43.31 38.47 3.94 50.62 46.07 4.22 58.70 58.70 4.53 67.40 67.40 4.86 75.47 75.47 5.25
2000 24.72 22.74 3.32 30.26 27.80 3.49 37.26 33.97 3.71 43.75 38.86 3.93 51.14 46.53 4.20 59.34 59.34 4.47 67.57 67.57 4.79 72.61 72.61 5.06
70
(21.1)
1500 22.84 21.01 3.40 28.50 26.19 3.61 36.04 32.86 3.88 42.34 37.61 4.15 49.45 45.00 4.46 57.25 57.25 4.83 66.02 66.02 5.19 74.43 74.43 5.65
1625 23.07 21.22 3.41 28.74 26.41 3.61 36.27 33.07 3.87 42.61 37.84 4.13 49.77 45.29 4.43 57.63 57.63 4.78 66.38 66.38 5.11 74.67 74.67 5.55
1750 23.30 21.44 3.42 28.99 26.64 3.62 36.48 33.26 3.87 42.85 38.06 4.11 50.06 45.55 4.40 58.00 58.00 4.74 66.64 66.64 5.06 74.68 74.68 5.47
2000 23.75 21.85 3.46 29.44 27.06 3.64 36.85 33.60 3.88 43.28 38.44 4.11 50.57 46.02 4.38 58.68 58.68 4.67 66.90 66.90 4.99 72.84 72.84 5.30
75
(23.9)
1500 21.87 20.12 3.54 27.71 25.46 3.76 34.56 31.51 4.03 41.89 37.21 4.34 48.89 44.49 4.66 56.55 56.55 5.03 65.16 65.16 5.40 73.45 73.45 5.88
1625 22.08 20.32 3.55 27.94 25.67 3.77 34.84 31.76 4.02 42.15 37.43 4.31 49.21 44.78 4.62 56.94 56.94 4.98 65.56 65.56 5.33 73.74 73.74 5.78
1750 22.32 20.53 3.57 28.18 25.90 3.77 35.20 32.09 4.02 42.39 37.65 4.30 49.50 45.05 4.60 57.30 57.30 4.94 65.85 65.85 5.27 73.83 73.83 5.70
2000 22.75 20.93 3.60 28.63 26.31 3.80 36.40 33.19 4.05 42.82 38.03 4.29 50.01 45.51 4.57 57.99 57.99 4.87 66.19 66.19 5.20 72.85 72.85 5.55
60 Size Outdoor Section With FVM4X60***L Indoor Section - LO
65
(18.3)
1200 13.69 12.59 2.67 19.50 17.92 2.75 25.04 22.83 2.84 30.30 26.91 2.94 35.80 32.58 3.07 39.55 39.55 3.18 42.98 42.98 3.30 46.15 46.15 3.40
1300 13.81 12.71 2.68 19.67 18.08 2.75 25.29 23.05 2.83 30.62 27.19 2.92 36.10 32.85 3.04 39.97 39.97 3.13 43.47 43.47 3.24 46.62 46.62 3.32
1400 13.95 12.83 2.69 19.87 18.26 2.75 25.53 23.27 2.83 30.92 27.46 2.90 36.39 33.11 3.01 40.32 40.32 3.09 43.89 43.89 3.19 47.03 47.03 3.26
1600 14.22 13.08 2.71 20.21 18.57 2.77 25.94 23.65 2.82 31.45 27.93 2.89 36.86 33.54 2.97 40.89 40.89 3.04 44.64 44.64 3.10 47.64 47.64 3.18
70
(21.1)
1200 12.56 11.56 2.79 18.42 16.93 2.87 23.98 21.87 2.97 29.23 25.96 3.07 35.00 31.85 3.22 38.74 38.74 3.33 42.09 42.09 3.46 45.24 45.24 3.57
1300 12.73 11.72 2.80 18.60 17.09 2.87 24.24 22.10 2.96 29.55 26.25 3.05 35.36 32.17 3.19 39.13 39.13 3.29 42.58 42.58 3.40 45.78 45.78 3.49
1400 12.89 11.86 2.81 18.80 17.28 2.88 24.50 22.33 2.96 29.87 26.53 3.04 35.67 32.46 3.16 39.50 39.50 3.25 43.01 43.01 3.35 46.18 46.18 3.43
1600 13.13 12.08 2.83 19.16 17.61 2.89 24.93 22.73 2.95 30.41 27.01 3.02 36.13 32.88 3.12 40.09 40.09 3.20 43.75 43.75 3.27 46.81 46.81 3.34
75
(23.9)
1200 12.10 11.14 2.92 17.17 15.78 3.00 22.80 20.79 3.10 28.07 24.93 3.21 33.24 30.25 3.34 37.87 37.87 3.50 41.18 41.18 3.63 44.31 44.31 3.75
1300 12.28 11.30 2.93 17.37 15.96 3.00 23.05 21.02 3.09 28.41 25.23 3.19 33.69 30.66 3.31 38.28 38.28 3.45 41.66 41.66 3.57 44.86 44.86 3.66
1400 12.44 11.44 2.94 17.58 16.15 3.00 23.32 21.26 3.09 28.73 25.51 3.18 34.38 31.28 3.30 38.63 38.63 3.41 42.08 42.08 3.52 45.31 45.31 3.60
1600 11.89 10.94 2.95 17.95 16.50 3.02 23.79 21.69 3.09 29.27 25.99 3.16 35.34 32.16 3.28 39.23 39.23 3.36 42.79 42.79 3.45 45.96 45.96 3.51
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
* Tested Combination
} The Btuh heating capacity values shown are net integrated values from which the defrost effect has been subtracted. The Btuh heating from supplement heaters should be added to those values to obtain total system capacity.
{ The kW values include the compressor, outdoor f an motor, and indoor blower motor. The kW f r om supplement heaters should be added to these values to obtain total system kilowatts.
EDB —EnteringDryBulb