Installation Manual

36 440 01 4800 02
Specifications subject to change without notice.
CARBON MONOXIDE POISONING HAZARD
Failure to follow the instructions outlined below for each
appliance being placed into operation could result in carbon
monoxide poisoning or death.
For all venting configurations for this appliance and other gas
appliances placed into operation for this structure, provisions
for adequate combustion, ventilation, and dilution air must be
provided in accordance with:
USA Installations: Section 9.3 current edition of NFPA
54/ANSI Z223.1, Air for Combustion and Ventilation and
applicable provisions of the local building codes.
Canadian Installations: Part 8 of current edition of
CAN/CSA-- B149.1. Venting Systems and Air Supply for
Appliances and all authorities having jurisdiction.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance
connected to the venting system being placed into operation
could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into operation,
while all other appliances connected to the venting system are
not in operation:
1. Seal any unused openings in venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 or the CSA B149 Nat-
ural Gas and Propane Installation Code and these in-
structions. Determine that there is no blockage or
restriction, leakage, corrosion and other deficiencies,
which could cause an unsafe condition.
3. As far as practical, close all building doors and
windows and all doors between the space in which the
appliance(s) connected to the venting system are
located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not
connected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they are operating at maximum speed. Do not operate
a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat
so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances
at the draft hood relief opening after 5 minutes of
main burner operation. Use the flame of a match or
candle.
8. If improper venting is observed during any of the
above tests, the venting system must be corrected in
accordance with the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 and/or CSA B149.1 Natural Gas
and Propane Installation Code.
9. After it has been determined that each appliance
connected to the venting system properly vents when
tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other
gas--fired burning appliance to their previous
conditions of use.
!
WARNING
Venting Systems
RECOMMENDED SUPPORT FOR
VENT TERMINATION
It is recommended that sidewall vent terminations of over 24
inches (0.6 M) in length or rooftop vent terminations of over
36 inches (1 M) in length be supported by EITHER the
factory accessory vent termination kit or field--supplied
brackets or supports attached to the structure. A factory
accessory vent termination kit may be used for direct vent
terminations. Termination kits are available for 2 -- in. or 3 -- in.
pipe. See Table 12 for available options.
NOTICE