Specifications

PRODUCT SPECIFICATIONS Fan Coils: FEM4X
8 496 51 5601 02
Specifications are subject to change without notice.
AIRFLOW PERFORMANCE CFM at a given Speed and Static reading
Model Blower Speed
Total Static (inches water column)
0.10 0.20 0.30 0.40 0.50 0.60
FEM4X1800B
Tap 5 767 739 702 669 620 565
Tap 4 614 569 534 486 436 398
Tap 3 701 660 616 581 537 499
Tap 2 614 569 534 486 436 398
Tap 1 410 350 304 261 228 203
FEM4X2400C
Tap 5 969 936 892 835 763 676
Tap 4 826 795 766 743 706 660
Tap 3 826 795 766 743 706 660
Tap 2 701 660 616 581 537 499
Tap 1 617 592 552 507 472 420
FEM4X3000B
Tap 5 1108 1090 1065 1034 1009 974
Tap 4 1026 1000 969 938 899 865
Tap 3 1026 1000 969 938 899 865
Tap 2 909 873 842 799 762 724
Tap 1 825 795 757 722 674 634
FEM4X3600B
Tap 5 1301 1276 1245 1218 1176 1121
Tap 4 1227 1191 1169 1143 1105 1074
Tap 3 1227 1191 1169 1143 1105 1074
Tap 2 1087 1062 1030 1001 966 930
Tap 1 1026 1000 969 938 899 865
FEM4X4200B
Tap 5 1560 1544 1507 1464 1424 1358
Tap 4 1419 1397 1358 1320 1279 1239
Tap 3 1419 1397 1358 1320 1279 1239
Tap 2 1249 1220 1184 1142 1093 1052
Tap 1 1242 1205 1158 1110 1069 1026
FEM4X4800B
Tap 5 1743 1712 1679 1642 1610 1574
Tap 4 1669 1634 1599 1564 1531 1499
Tap 3 1669 1634 1599 1564 1531 1499
Tap 2 1452 1413 1377 1339 1308 1271
Tap 1 1300 1256 1221 1182 1142 1101
FEM4X6000B
Tap 5 1897 1867 1836 1808 1774 1736
Tap 4 1817 1785 1757 1724 1693 1655
Tap 3 1817 1785 1757 1724 1693 1655
Tap 2 1657 1621 1589 1557 1518 1474
Tap 1 1443 1412 1377 1332 1286 1243
- Airflow outside 450 cfm/ton.
NOTES:
1. Airflow based upon dry coil at 230v with factoryapproved filter and electric heater (2 element heater sizes 1800 through 3600, 3 element
heater sizes 4200 through 6000). Airflow at 208 volts is approximately the same as 230 volts because the ECM motor is a constant torque
motor. The torque doesn’t drop off at the speeds the motor operates.
2. To avoid potential for condensate blowing out of drain pan prior to making drain trap:
Return static pressure must be less than 0.40 in. wc.
Horizontal applications of 4200 6000 sizes must have supply static greater than 0.20 in. wc.
3. Airflow above 400 cfm/ton on 48006000 size could result in condensate blowing off coil or splashing out of drain pan.
STATIC PRESSURE CORRECTION FROM DRY TO WET COIL (inches of water column)
Unit Size
CFM
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
1800B
0.034 0.049 0.063
2400C
0.049 0.063 0.076 0.089
3000B
0.049 0.059 0.070 0.080
3600B
0.070 0.080 0.090 0.099
4200B
0.049 0.056 0.063 0.070
4800B
0.063 0.070 0.076 0.083 0.090
6000B
0.049 0.054 0.059 0.065 0.070