Product Specifications
PRODUCT SPECIFICATIONS Gas Furnace: G80CTL
2 441 51 3500 01
Specifications subject to change without notice.
MODEL NUMBER IDENTIFICATION GUIDE
A190043
For California Residents:
For installation in SCAQMD only: This furnace does not meet the SCAQMD Rule 1111 14 ng/J NOx emission limit, and thus is subject to
a mitigation fee of up to $450. This furnace is not eligible for the Clean Air Furnace Rebate Program: www.CleanAirFurnaceRebate.com
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS FOR ALL UNITS
This forced air furnace is equipped for use with natural gas at alti-
tudes 0 − 10,000 ft (0 − 3,050m).
An accessory kit, supplied by the manufacturer, shall be used to
convert to propane gas use or may be required for some natural
gas applications.
This furnace is for indoor installation in a building constructed on
site.
The furnace may be installed on combustible flooring in alcove or
closet at minimum clearance as indicated by the diagram from
combustible material.
This furnace may be used with a Type B−1 Vent and may be ven-
ted in common with other gas fired appliances.
This furnace is approved for UPFLOW, DOWNFLOW, and
HORIZONTAL installations.
Downflow Positions:
{ Installation on non−combustible floors only.
For Installation on combustible flooring only when installed on
special base or coil assembly.
∅ 18 inch front clearance required for alcove.
* Indicate supply or return sides when furnace is in the horizont-
al position. Line contact only permissible between lines
formed by intersections of the Top and two Sides of the furnace
jacket, and building joists, studs or framing.