8
Accessory Description and Usage (Listed Alphabetically) (Continued)
9. Support Feet
Four stick-on plastic feet that raise the unit 4 in. (101.6 mm) above the
mounting pad. This allows sand, dirt, and other debris to be flushed from
the unit base, minimizing corrosion.
Usage Guideline:
Suggested in the following applications:
Coastal installations.
Windy areas or where debris is normally circulating.
Rooftop installations.
For improved sound ratings.
10. Thermostatic Expansion Valve (TXV)
A modulating flow-control valve which meters refrigerant liquid flow
rate into the evaporator in response to the superheat of the refrigerant gas
leaving the evaporator.
Kit includes valve, adapter tubes, and external equalizer tube. Hard shut
off types are available.
NOTE: When using a hard shut off TXV with single phase reciprocating
compressors, a Compressor Start Assist Capacitor and Relay is required.
Usage Guideline:
Required to achieve AHRI ratings in certain equipment
combinations. Refer to combination ratings.
Hard shut off TXV or LLS required in air conditioner long line
applications.
Required for use on all zoning systems.
11. Time-Delay Relay
An SPST delay relay which briefly continues operation of indoor blower
motor to provide additional cooling after the compressor cycles off.
NOTE: Most indoor unit controls include this feature. For those that do
not, use the guideline below.
Usage Guideline:
For improved efficiency ratings for certain combinations of indoor
and outdoor units. Refer to AHRI Unitary Directory.
12. Winter Start Control
This control is designed to alleviate nuisance opening of the
low-pressure switch by bypassing it for the first 3 minutes of operation.