N4A6: Product Specifications
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
9
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{ Time-Delay fuse.
FLA- Full Load Amps
LRA - Locked Rotor Amps
MCA- Minimum Circuit Amps
RLA- Rated Load Amps
NOTE:Control circuit is 24V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2010 requirements of ASHRAE Standards 90.1
NOTE: Tested in compliance with AHRI 270–1995 (not listed with AHRI)
* TXV must be ordered separately when indoor coil is not equipped with a TXV. TXV must be hard–shutoff type.
Electrical Data
UNIT SIZE - SERIES V/PH
OPER VOLTS* COMPR FAN
MCA
MAX FUSE{
or CKT BRK
AMPS
MAX MIN LRA RLA FLA
18GKB
208/230/1-60 253 197
47.5 9.0 0.40 11.7 20
24GKB 62.9 10.9 0.50 14.1 25
30GKB 63.0 10.9 0.50 14.1 25
36GKB 79.0 13.6 0.90 17.9 30
42GKB 109.0 16.7 0.50 21.4 35
48GKB 124.0 18.5 2.80 25.9 40
60-GKB 152.5 23.7 2.80 32.4 50
36GHB
208/230-3-60 253 187
70.0 8.10 0.90 11.0 15
48GHB 83.1 13.80 2.80 20.1 30
60GHB 110.0 15.90 2.80 22.7 35
36GLB
460-3-60 506 414
31.0 4.00 0.50 5.5 15
48GLB 41.0 6.20 1.60 9.4 15
60GLB 52.0 7.10 1.60 10.5 15
A–Weighted Sound Power (dBA) With Sound Shield
UNIT SIZE
STANDARD
RATING
TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)
125 250 500 1000 2000 4000 8000
18 75 45 53 58 62 61 55 49
24 72 48 55 59 63 59 55 49
30 73 50 54 62 66 60 57 51
36 69 48 59 57 59 56 51 40
42 72 63 57 59 61 57 55 51
48 73 55 61 64 63 60 57 48
60 73 67 68 68 71 63 55 52
A–Weighted Sound Power (dBA) Without Sound Shield
UNIT SIZE
STANDARD
RATING
TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)
125 250 500 1000 2000 4000 8000
18 75 47 56 60 64 60 54 47
24 74 48 54 60 64 59 56 50
30 74 48 55 62 67 61 57 51
36 71 49 60 59 61 59 55 47
42 74 64 57 60 61 58 56 53
48 73 55 61 64 63 60 57 48
60 74 66 67 68 72 64 60 57
METERING DEVICE
UNIT SIZE-SERIES INDOOOR REQUIRED SUBCOOLING F (°C)
18GKB
TXV*
8.0 (4.44)
24GKB 9.0 (5.00)
30GKB 11.0 (6.11)
36GKB 10.0 (5.56)
42GKB 13.0 (7.22)
48GKB 8.0 (4.44)
60GKB 10.0 (5.56)
36G(H,L)B (3-PH 10.0 (5.56)
48G(H,L)B (3-PH 8.0 (4.44)
60G(H,L)B (3-PH 9.0 (5.00)