N4A6: Product Specifications
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
3
Refrigerant Piping Length Limitations
Liquid Line Sizing and Maximum Total Equivalent Lengths{ for Cooling Only Systems with R-410A
Refrigerant:
The maximum allowable length of a residential split system depends on the liquid line diameter and vertical separation between indoor and outdoor
units.
See Table below for liquid line sizing and maximum lengths :
*Maximum actual length not to exceed 200 ft (61 m)
{Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.
-- = outside acceptable range
* Maximum actual length not to exceed 200 ft (61 m)
{Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.
-- = outside acceptable range
Table 1 – Maximum Total Equivalent Length
Outdoor Unit BELOW Indoor Unit
Size
Liquid Line
Connection
Liquid Line
Diam.
w/ TXV
AC with R-410A Refrigerant
Maximum Total Equivalent Length{: Outdoor unit BELOW Indoor
Vertical Separation ft (m)
0-5
(0-1.5)
6-10
(1.8-3.0)
11-20
(3.4-6.1)
21-30
(6.4-9.1)
31-40
(9.4-12.2)
41-50
(12.5-15.2)
51-60
(15.5-18.3)
61-70
(18.6-21.3)
71-80
(21.6-24.4)
18 3/8
1/4 150 150 125 100 100 75 -- -- --
5/16 250* 250* 250* 250* 250* 250* 250* 225* 150
3/8 250* 250* 250* 250* 250* 250* 250* 250* 250*
24 3/8
1/4 75 75 75 50 50 -- -- -- --
5/16 250* 250* 250* 250* 250* 225* 175 125 100
3/8 250* 250* 250* 250* 250* 250* 250* 250* 250*
30 3/8
1/4 30 -- -- -- -- -- -- -- --
5/16 175 225* 200 175 125 100 75 -- --
3/8 250* 250* 250* 250* 250* 250* 250* 250* 250*
36 3/8
5/16 175 150 150 100 100 100 75 -- --
3//8 250* 250* 250* 250* 250* 250* 250* 250* 250*
42,43 3/8
5/16 125 100 100 75 75 50 -- -- --
3/8 250* 250* 250* 250* 250* 250* 250* 250* 150
48 3/8 3/8 250* 250* 250* 250* 250* 250* 230 160 --
54, 60, 61 3/8 3/8 250* 250* 250* 225* 190 150 110 -- --
Table 2 – Maximum Total Equivalent Length
Outdoor Unit ABOVE Indoor Unit
Size
Liquid Line
Connection
Liquid Line
Diam.
w/ TXV
AC with R-410A Refrigerant
Maximum Total Equivalent Length{: Outdoor unit ABOVE Indoor
Vertical Separation ft (m)
25
(7.6)
26-50
(7.9-15.2)
51-75
(15.5-22.9)
76-100
(23.2-30.5)
101-125
(30.8-38.1)
126-150
(38.4-45.7)
151-175
(46.0-53.3)
176-200
(53.6-61.0)
18 3/8
1/4 175 250* 250* 250* 250* 250* 250* 250*
5/16 250* 250* 250* 250* 250* 250* 250* 250*
3/8 250* 250* 250* 250* 250* 250* 250* 250*
24 3/8
1/4 100 125 175 200 225* 250* 250* 250*
5/16 250* 250* 250* 250* 250* 250* 250* 250*
3/8 250* 250* 250* 250* 250* 250* 250* 250*
30 3/8
1/4 30 -- -- -- -- -- -- --
5/16 250* 250* 250* 250* 250* 250* 250* 250*
3/8 250* 250* 250* 250* 250* 250* 250* 250*
36 3/8
5/16 225* 250* 250* 250* 250* 250* 250* 250*
3/8 250* 250* 250* 250* 250* 250* 250* 250*
42, 43 3/8
5/16 175 200 250* 250* 250* 250* 250* 250*
3/8 250* 250* 250* 250* 250* 250* 250* 250*
48 3/8 3/8 250* 250* 250* 250* 250* 250* 250* 250*
54, 60, 61 3/8 3/8 250* 250* 250* 250* 250* 250* 250* 250*