N4A6 Product Specs

Table Of Contents
N4A6: Product Specifications
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
7
ACCESSORY USAGE GUIDELINE
* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 35 ft. (10.7 m) vertical differential, refer to Residential Split-System Longline Application Guideline.
{ Additional requirement for Low-Ambient Controller (full modulation feature) MotorMasterr Control.
} If unit equipped with ECM OD motor, both motor and fan need to be replaced per unit accessory guide to work properly. Unit will not meet AHRI rated efficiency once motor and fan are
replaced to use this accessory.
Accessory Description and Usage (Listed Alphabetically)
1. Ball-Bearing Fan Motor
A fan motor with ball bearings which permits speed reduction while
maintaining bearing lubrication.
Usage Guideline:
Required on all units when MotorMasterr is used.
2. Compressor Start Assist - Capacitor and Relay
Start capacitor and relay gives a hard” boost to compressor motor at
each start up.
Usage Guideline:
Required for reciprocating compressors in the following applications:
Long line
Low ambient cooling
Hard shut off expansion valve on indoor coil
Liquid line solenoid on indoor coil
Required for single-phase scroll compressors in the following
applications:
Long line
Low ambient cooling
Suggested for all compressors in areas with a history low voltage
problems.
3. Compressor Start Assist — PTC Type
Solid state electrical device which gives a ”soft” boost to the compressor
at each start-up.
Usage Guideline:
Suggested in installations with marginal power supply.
4. Crankcase Heater
An electric resistance heater which mounts to the base of the compressor
to keep the lubricant warm during off cycles. Improves compressor
lubrication on restart and minimizes the chance of liquid slugging.
Usage Guideline:
Required in low ambient cooling applications.
Required in long line applications.
Suggested in all commercial applications.
5. Cycle Protector
The cycle protector is designed to prevent compressor short cycling.
This control provides an approximate 5-minute delay after power to the
compressor has been interrupted for any reason, including power outage,
protector control trip, thermostat jiggling, or normal cycling.
6. Evaporator Freeze Thermostat
An SPST temperature-actuated switch that stops unit operation when
evaporator reaches freeze-up conditions.
Usage Guideline:
Required when low ambient kit has been added.
7. Low-Ambient Pressure Switch Kit
A long life pressure switch which is mounted to outdoor unit service
valve. It is designed to cycle the outdoor fan motor in order to maintain
head pressure within normal operating limits (approximately 100 psig to
225 psig). The control will maintain working head pressure at
low-ambient temperatures down to 0_F (-18_C) when properly installed.
Usage Guideline:
A Low-Ambient Pressure Switch or MotorMasterr Low-Ambient
Controller must be used when cooling operation is used at outdoor
temperatures below 55_F (12.8_C).
8. Outdoor Air Temperature Sensor
This device enables the thermostat to display the outdoor temperature.
This device is also required to enable special thermostat features such as
auxiliary heat lock out.
Usage Guideline:
Suggested for all compatible thermostats.
ACCESSORY
REQUIRED FOR LOW-AMBIENT
COOLING APPLICATIONS
(Below 55F/12.8_C)
REQUIRED FOR LONG
LINE
APPLICATIONS*
(Over 80 ft./24.38 m)
REQUIRED FOR
SEA COAST
APPLICATIONS
(Within 2 miles/3.22 km)
Ball Bearing Fan Motor Yes
{ No No
Compressor Start Assist Capacitor and Relay Yes Yes No
Crankcase Heater Yes Yes No
Evaporator Freeze Thermostat Yes No No
Hard Shut-Off TXV Yes Yes Yes
Liquid Line Solenoid Valve No No No
Low-ambient Pressure Switch Yes
} No No
Support Feet Recommended No Recommended
Winter Start Control Yes No No