Specifications
PRODUCT SPECIFICATIONS Split System Heat Pump: HVH8
428 51 5900 03 23
Specifications subject to change without notice.
HVH836
DETAILED COOLING CAPACITIES
#
− EFFICIENCY MODE
EDB
°F (°C)
EVAP.
AIR
HVH836 / FCM4X48***L Efficiency Mode
Condenser Entering Air Temperature °F (°C)
115 (46.1) 105 (40.5) 95 (35) 85 (29.4) 75 (23.9) 65 (18.3)
EWB
°F
(°C)
ID
SCF
M
Capacity MBtuh
Total
Sys.
KW**
ID
SCF
M
Capacity MBtuh
Total
Sys.
KW**
ID
SCF
M
Capacity MBtuh
Total
Sys.
KW**
ID
SCF
M
Capacity MBtuh
Total
Sys.
KW**
ID
SCF
M
Capacity MBtuh
Total
Sys.
KW**
ID
SCF
M
Capacity MBtuh
Total
Sys.
KW**
Total
Sens
‡
Total
Sens
‡
Total
Sens
‡
Total
Sens
‡
Total
Sens
‡
Total
Sens
‡
STAGE 5
75
(23.9)
72
(22.2)
1050
33.66 13.76 3.92
1050
35.83 14.56 3.62
1050
37.64 15.24 3.33
1050
39.71 16.02 3.03
1050
41.70 16.78 2.74
1050
43.66 17.54 2.45
67
(19.4)
30.67 18.58 3.83 32.63 19.41 3.55 34.28 20.14 3.26 36.14 20.93 2.98 37.96 21.76 2.70 39.71 22.50 2.42
63
(17.2)
28.43 22.37 3.76 30.25 23.22 3.49 31.80 23.97 3.20 33.50 24.78 2.93 35.17 25.58 2.67 36.77 26.36 2.41
57
(13.9)
26.29 26.29 3.70 27.67 27.67 3.42 28.85 28.85 3.14 30.12 30.12 2.88 31.51 31.06 2.63 32.87 31.93 2.38
80
(26.7)
72
(22.2)
1050
33.58 18.53 3.92
1050
35.75 19.37 3.62
1050
37.55 20.09 3.33
1050
39.61 20.91 3.03
1050
41.61 21.68 2.74
1050
43.56 22.44 2.45
67
(19.4)
30.58 23.31 3.83 32.54 24.17 3.55 34.20 24.92 3.26 36.06 25.73 2.98 37.87 26.55 2.70 39.64 27.35 2.42
63
(17.2)
28.45 27.05 3.77 30.25 27.93 3.49 31.78 28.71 3.20 33.48 29.54 2.93 35.15 30.40 2.67 36.73 31.18 2.41
57
(13.9)
27.92 27.92 3.75 29.37 29.37 3.47 30.60 30.60 3.18 31.93 31.93 2.91 33.21 33.21 2.65 34.45 34.45 2.39
STAGE 3
75
(23.9)
72
(22.2)
900
21.50 9.09 2.51
900
22.99 9.62 2.19
900
24.00 9.99 1.85
900
25.46 10.52 1.58
900
26.89 11.04 1.32
900
28.22 11.54 1.09
67
(19.4)
19.38 12.78 2.49 20.72 13.34 2.18 21.71 13.77 1.84 23.03 14.33 1.57 24.32 14.88 1.33 25.58 15.44 1.11
63
(17.2)
17.85 15.69 2.47 19.07 16.26 2.18 20.03 16.73 1.83 21.24 17.32 1.57 22.42 17.89 1.34 23.59 18.46 1.12
57
(13.9)
17.16 17.16 2.47 18.15 18.15 2.17 18.94 18.94 1.82 19.90 19.90 1.57 20.84 20.84 1.34 21.76 21.76 1.13
80
(26.7)
72
(22.2)
900
21.43 12.83 2.51
900
22.91 13.39 2.19
900
23.93 13.80 1.85
900
25.39 14.36 1.58
900
26.81 14.92 1.32
900
28.20 15.48 1.09
67
(19.4)
19.34 16.49 2.49 20.67 17.07 2.18 21.66 17.54 1.84 22.97 18.13 1.57 24.25 18.71 1.33 25.52 19.29 1.11
63
(17.2)
18.40 18.40 2.48 19.44 19.44 2.18 20.23 20.23 1.83 21.35 21.04 1.57 22.50 21.67 1.34 23.66 22.27 1.12
57
(13.9)
18.36 18.36 2.48 19.40 19.40 2.18 20.20 20.20 1.83 21.20 21.20 1.57 22.18 22.18 1.34 23.13 23.13 1.12
STAGE 1
75
(23.9)
72
(22.2)
800
14.47 6.38 1.82
800
15.58 6.77 1.53
600
10.69 4.69 0.66
600
11.51 4.98 0.49
600
12.34 5.28 0.34
600
13.17 5.58 0.22
67
(19.4)
13.00 9.42 1.82 14.02 9.86 1.54 9.54 6.85 0.69 10.28 7.17 0.52 11.02 7.49 0.37 11.76 7.81 0.25
63
(17.2)
12.02 11.77 1.82 12.97 12.18 1.55 8.78 8.53 0.70 9.43 8.87 0.54 10.10 9.21 0.39 10.77 9.55 0.27
57
(13.9)
11.94 11.94 1.82 12.73 12.73 1.55 8.69 8.69 0.71 9.25 9.25 0.54 9.81 9.81 0.40 10.36 10.36 0.28
80
(26.7)
72
(22.2)
800
14.41 9.47 1.82
800
15.54 9.92 1.52
600
10.64 6.90 0.71
600
11.46 7.22 0.54
600
12.29 7.55 0.40
600
13.12 7.88 0.28
67
(19.4)
13.03 12.45 1.82 14.03 12.93 1.54 9.56 9.02 0.71 10.28 9.37 0.54 11.01 9.72 0.40 11.75 10.07 0.28
63
(17.2)
12.86 12.86 1.82 13.70 13.70 1.54 9.40 9.40 0.69 9.99 9.99 0.52 10.58 10.58 0.38 11.17 11.17 0.26
57
(13.9)
12.84 12.84 1.82 13.67 13.67 1.54 9.38 9.38 0.69 9.97 9.97 0.52 10.56 10.56 0.38 11.15 11.15 0.26
Operation in this area is restricted to maintain reliable system operation and customer comfort. The system will default to the next available stage
Stage 1 - Compressor speed limited to stage two at 105 and 115 outdoor.
See additional notes on page 43