PRODUCT SPECIFICATIONS Split System Heat Pump: HVH8
428 51 5900 03 11
Specifications subject to change without notice.
TESTED AHRI COMBINATION RATINGS*
NOTE: Ratings contained in this document are subject to change at any time.
For AHRI ratings certificates, please refer to the AHRI directory. www.ahridirectory.org
Additional ratings and system combinations can be accessed via the Airquest database at:
http://www.icpeqp.com/AHRIratings/ratings.aspx?Brand=Airquest
Or scan this QR code:
Outdoor Model Indoor Model Furnace Model Stages
Cooling Heating
Cooling
Cap.
SEER EER ID CFM HSPF
High Temp Low Temp
Capacity
47°F (8°C)
COP
Capacity
17°F (-8°C)
COP
HVH824GKA101
FCM4X24***L + WALLCON 5 24,000 17.5 11.0 825 10.5 24,400 3.61 15,800 2.60
HVH824GKA101
FVM4X24***L 2 23,200 15.0 10.5 700 9.0 23,800 3.42 15,600 2.52
HVH825GKA101
FCM4X48***L + WALLCON 5 24,000 18.0 12.5 825 10.0 26,800 3.56 19,900 2.58
HVH825GKA101
FVM4X36***L 2 23,200 16.5 12.0 700 8.2 30,200 3.04 19,900 2.38
HVH836GKA101
FCM4X48***L + WALLCON 5 34,200 17.5 10.5 1050 10.5 34,200 3.56 23,000 2.58
HVH836GKA101
FVM4X48***L 2 34,600 15.5 10.0 1050 9.0 34,000 3.58 22,400 2.58
HVH837GKA101
FCM4X60***L + WALLCON 5 33,600 19.0 13.0 1050 11.0 40,000 3.50 30,400 2.66
HVH848GKA101
FCM4X48***L + WALLCON 5 46,000 18.0 11.0 1400 11.0 50,500 3.44 35,200 2.66
HVH860GKA101
FCM4X60***L + WALLCON 5 57,000 17.0 10.0 1600 10.0 60,000 3.10 44,500 2.48
HVH860GKA101
FVM4X60***L 2 57,000 15.0 10.0 1750 9.0 60,000 3.05 44,000 2.45
Ratings with “+ WALLCON” are communicating systems with Observer® Wall Control and 5-stages of operation.
Ratings without “+ WALLCON” are non-communicating systems with 2-stage operation.
* Ratings are net values reflecting the effects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on:
Cooling Standard: 80_F (27_C) db 67_F (19_C) wb indoor entering air temperature and 95_F (35_C) db air entering outdoor unit.
High-Temp Heating Standard: 70_F (21_C) db indoor entering air temperature and 47_F (8_C) db 43°F (6_C) wb air entering outdoor unit.
Low-Temp Heating Standard: 70_F (21_C) db indoor entering air temperature and 17_F (-8_C) db 15°F (-9_C) wb air entering outdoor unit.
COP — Coefficient of Performance
EER — Energy Efficiency Ratio
HSPF — Heating Seasonal Performance Factor
SEER — Seasonal Energy Efficiency Ratio
WALLCON— Wall Control
NOTE: Ratings contained in this document are subject to change at any time.