Specifications
PRODUCT SPECIFICATIONS Gas Furnace: G96CTN
440 51 4900 01 9
Specifications subject to change without notice.
Cooling
4
and Heating Air Delivery − CFM continued (Bottom Return
5
with Filter)
(SW1-5 and SW4-3 set to OFF, except as indicated. See notes 1 and 2.)
Unit size:
1202422
Clg/CF Switch settings External Static Pressure (ESP)
Clg Switches SW2-3 SW2-2 SW2-1 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Clg Default: OFF OFF OFF 1845 1840 1835 1835 1825 1820 1810 1800 1785 1775
CF Switches SW3-3 SW3-2 SW3-1
Low-Clg Default: OFF OFF OFF 895 915 915 915 915 See note 4
Cooling Airflow (SW2)
Low-Cooling Airflow
(SW3)
OFF OFF ON 715 725 720 710 705 See note 4
OFF ON OFF 895 915 915 915 915 See note 4
OFF ON ON 1070 1090 1105 1115 1115 1110 1115 1120 1120 1110
ON OFF OFF 1240 1265 1280 1295 1295 1305 1305 1305 1315 1315
ON OFF ON 1520 1520 1515 1505 1495 1490 1480 1465 1455 1445
ON ON OFF 1845 1840 1835 1835 1825 1820 1810 1800 1785 1775
ON ON ON 2150 2145 2140 2145 2135 2130 2115 2100 2065 1985
Maximum Clg Airflow
2
2150 2145 2140 2145 2135 2130 2115 2100 2065 1985
CF Switches SW3-3 SW3-2 SW3-1
Cont. Fan Default: OFF OFF OFF 895 915 915 915 915 See note 4
Continuous Fan Airflow
(SW3)
OFF OFF ON 715 725 720 710 705 See note 4
OFF ON OFF 805 820 815 810 810 See note 4
OFF ON ON 895 915 915 915 915 See note 4
ON OFF OFF 895 915 915 915 915 See note 4
ON OFF ON 895 915 915 915 915 See note 4
ON ON OFF 895 915 915 915 915 See note 4
ON ON ON 895 915 915 915 915 See note 4
Heating (SW1)
High Heat Airflow
3
1825 1820 1815 1800 1800 1795 1785 1775 1760 1745
Low Heat Airflow
3
1555 1555 1550 1550 1545 1525 1520 1505 1495 1485
1. Nominal 350 CFM/ton cooling airflow is delivered with SW1-5 and SW4-3 set to OFF.
Set SW15 to ON for nominal 400 CFM/ton (+15% airflow).
Set SW43 to ON for nominal 325 CFM/ton (7% airflow).
Set both SW15 and SW43 to ON for nominal 370 CFM/ton (+7% airflow).
This applies to Cooling and Low-Cooling airflows, but does not affect continuous fan airflows.
The above adjustments in airflow are subject ot motor horsepower range/capacity
2. Maximum cooling airflow is achieved when switches SW21, SW22, SW23 and SW15 are set to ON, and SW43 is set to OFF.
3. All heating CFM's are when comfort/efficiency adjustment switch (SW14) is set to OFF.
4. Ductwork must be sized for highheating CFM within the operational range of ESP. Operation within the blank areas of the chart is not recom
mended because highheat operation will be above 1.0 ESP.
5. All airflows on 21" (533 mm) casing size furnaces are 5% less on side return only installations.