Specifications
PRODUCT SPECIFICATIONS Split System Heat Pump: HVH8
38 428 51 5900 03
Specifications subject to change without notice.
HVH848
HEAT PUMP HEATING PERFORMANCE − EFFICIENCY MODE
INDOOR AIR
HVH848 / FCM4X48***L Heating Efficiency Mode
Outdoor Coil Entering Air Temperature °F (°C)
7 (-13.9) 17 (-8.3) 27 (-2.8)
EDB
°F (°C)
ID SCFM
Capacity MBtuh
Total Sys. KW† ID SCFM
Capacity MBtuh
Total Sys. KW† ID SCFM
Capacity MBtuh
Total Sys. KW†
Total Integ‡ Total Integ‡ Total Integ‡
STAGE 5
65 (18.3)
700
22.65 20.82 2.72
1600
35.57 32.43 3.74
1600
40.44 35.92 3.87
70 (21.1) 22.10 20.31 2.77 35.20 32.09 3.88 40.08 35.59 4.02
75 (23.3) 20.89 19.19 2.73 34.73 31.67 4.00 39.66 35.23 4.17
STAGE 3
65 (18.3)
600
17.23 15.83 2.08
700
20.52 18.71 2.19
1275
24.10 21.40 2.18
70 (21.1) 16.82 15.46 2.13 20.25 18.46 2.29 23.86 21.19 2.29
75 (23.3) 16.32 15.00 2.17 19.94 18.18 2.37 23.61 20.97 2.40
STAGE 1
65 (18.3)
600
17.23 15.83 2.08
700
20.51 18.70 2.19
1275
20.26 17.99 1.88
70 (21.1) 16.82 15.46 2.13 20.24 18.45 2.28 20.03 17.79 1.97
75 (23.3) 16.32 15.00 2.17 19.93 18.17 2.37 19.81 17.60 2.07
INDOOR AIR
HVH848 / FCM4X48***L Heating Efficiency Mode
Outdoor Coil Entering Air Temperature °F (°C)
37 (2.8) 47 (8.3) 57 (13.9)
EDB
°F (°C)
ID SCFM
Capacity MBtuh
Total Sys. KW† ID SCFM
Capacity MBtuh
Total Sys. KW† ID SCFM
Capacity MBtuh
Total Sys. KW†
Total Integ‡ Total Integ‡ Total Integ‡
STAGE 5
65 (18.3)
1600
46.06 41.92 4.02
1600
51.02 51.02 4.13
1275
35.74 35.74 2.39
70 (21.1) 45.63 41.52 4.18 50.50 50.50 4.30 35.29 35.29 2.51
75 (23.3) 45.16 41.10 4.34 49.96 49.96 4.47 34.80 34.80 2.64
STAGE 3
65 (18.3)
1275
27.80 25.30 2.26
1275
31.75 31.75 2.33
1275
35.74 35.74 2.39
70 (21.1) 27.51 25.03 2.37 31.38 31.38 2.45 35.28 35.28 2.51
75 (23.3) 27.20 24.76 2.49 31.01 31.01 2.58 34.80 34.80 2.64
STAGE 1
65 (18.3)
1275
23.56 21.44 1.94
1000
16.14 16.14 0.88
1000
18.69 18.69 0.87
70 (21.1) 23.29 21.19 2.04 15.90 15.90 0.95 18.40 18.40 0.94
75 (23.3) 23.01 20.94 2.15 15.65 15.65 1.02 18.10 18.10 1.02
Operation in this area is restricted to maintain reliable system operation and customer comfort. The system will default to the next available stage
Stage 5 - Compressor speed limited to stage four at 7 and stage three at 57 outdoor; Stage 1 - Compressor speed limited to stage three at 7 and 17 and to stage two at 27 and 37 outdoor.
See additional notes on page 45