Specifications

PRODUCT SPECIFICATIONS Split System Heat Pump: HVH8
428 51 5900 03 29
Specifications subject to change without notice.
HVH837
DETAILED COOLING CAPACITIES
#
EFFICIENCY MODE
EDB
°F (°C)
EVAP.
AIR
HVH837 / FCM4X48***L Efficiency Mode
Condenser Entering Air Temperature °F (°C)
115 (46.1) 105 (40.5) 95 (35) 85 (29.4) 75 (23.9) 65 (18.3)
EWB
°F
(°C)
ID
SCF
M
Capacity MBtuh Total
Sys.
KW**
ID
SCF
M
Capacity MBtuh Total
Sys.
KW**
ID
SCF
M
Capacity MBtuh Total
Sys.
KW**
ID
SCF
M
Capacity MBtuh Total
Sys.
KW**
ID
SCF
M
Capacity MBtuh Total
Sys.
KW**
ID
SCF
M
Capacity MBtuh Total
Sys.
KW**
Total
Sens
Total
Sens
Total
Sens
Total
Sens
Total
Sens
Total
Sens
STAGE 5
75
(23.9)
72
(22.2)
1050
33.34 13.68 3.38
1050
35.38 14.43 2.99
1050
37.11 15.07 2.60
1050
39.00 15.77 2.25
1050
40.82 16.46 1.93
1050
42.56 17.12 1.64
67
(19.4)
30.28 18.76 3.34 32.11 19.52 2.97 33.70 20.19 2.58 35.41 20.92 2.26 37.04 21.61 1.95 38.64 22.30 1.66
63
(17.2)
28.02 22.76 3.31 29.71 23.52 2.95 31.19 24.21 2.57 32.77 24.95 2.25 34.29 25.67 1.95 35.77 26.37 1.67
57
(13.9)
26.22 26.22 3.28 27.53 27.53 2.93 28.66 28.66 2.56 29.86 29.86 2.25 31.00 31.00 1.96 32.09 32.09 1.69
80
(26.7)
72
(22.2)
1050
33.22 18.74 3.38
1050
35.26 19.50 2.99
1050
36.99 20.17 2.60
1050
38.88 20.89 2.25
1050
40.70 21.60 1.93
1050
42.44 22.28 1.64
67
(19.4)
30.18 23.76 3.34 32.01 24.54 2.97 33.60 25.23 2.58 35.31 25.97 2.26 36.94 26.69 1.95 38.54 27.40 1.66
63
(17.2)
28.06 27.66 3.31 29.73 28.49 2.95 31.18 29.21 2.57 32.75 29.98 2.25 34.26 30.72 1.95 35.73 31.44 1.67
57
(13.9)
27.88 27.88 3.31 29.25 29.25 2.95 30.44 30.44 2.57 31.68 31.68 2.25 32.88 32.88 1.96 34.02 34.02 1.68
STAGE 3
75
(23.9)
72
(22.2)
900
22.97 9.60 3.06
900
24.68 10.23 2.52
900
26.27 10.83 1.97
900
27.96 11.46 1.55
900
29.61 12.08 1.19
900
31.25 12.70 0.88
67
(19.4)
20.76 13.46 3.06 22.31 14.15 2.53 23.77 14.82 1.99 25.28 15.50 1.58 26.77 16.18 1.23 28.24 16.87 0.92
63
(17.2)
19.15 16.49 3.06 20.58 17.23 2.54 21.93 17.94 2.00 23.33 18.68 1.60 24.69 19.40 1.25 26.04 20.13 0.95
57
(13.9)
18.30 18.30 3.06 19.47 19.47 2.54 20.57 20.57 2.01 21.69 21.69 1.61 22.78 22.78 1.27 23.85 23.85 0.98
80
(26.7)
72
(22.2)
900
22.86 13.49 3.06
900
24.58 14.18 2.52
900
26.17 14.84 1.97
900
27.85 15.54 1.55
900
29.51 16.22 1.19
900
31.14 16.90 0.88
67
(19.4)
20.69 17.29 3.06 22.23 18.04 2.53 23.70 18.78 1.99 25.20 19.52 1.58 26.69 20.27 1.23 28.16 21.01 0.92
63
(17.2)
19.55 19.55 3.06 20.79 20.79 2.54 22.01 21.83 2.00 23.37 22.66 1.60 24.72 23.46 1.25 26.05 24.25 0.95
57
(13.9)
19.52 19.52 3.06 20.75 20.75 2.54 21.91 21.91 2.00 23.09 23.09 1.60 24.24 24.24 1.26 25.37 25.37 0.96
STAGE 1
75
(23.9)
72
(22.2)
800
17.86 7.53 2.92
800
19.41 8.11 2.31
600
14.82 6.15 1.11
600
16.14 6.65 0.76
600
17.47 7.17 0.48
600
18.85 7.63 0.26
67
(19.4)
16.10 10.65 2.94 17.51 11.32 2.34 13.41 8.44 1.15 14.59 9.03 0.80 15.79 9.63 0.52 17.00 10.24 0.30
63
(17.2)
14.87 13.08 2.95 16.15 13.82 2.36 12.38 10.26 1.18 13.46 10.91 0.83 14.56 11.57 0.55 15.67 12.24 0.33
57
(13.9)
14.32 14.32 2.95 15.40 15.40 2.37 11.67 11.67 1.20 12.58 12.58 0.85 13.49 13.49 0.57 14.41 14.41 0.35
80
(26.7)
72
(22.2)
800
17.78 10.67 2.92
800
19.33 11.35 2.31
600
14.76 8.44 1.11
600
16.08 9.04 0.76
600
17.41 9.64 0.48
600
18.76 10.26 0.26
67
(19.4)
16.07 13.74 2.94 17.46 14.50 2.34 13.37 10.73 1.15 14.55 11.41 0.80 15.74 12.09 0.52 16.94 12.78 0.30
63
(17.2)
15.31 15.31 2.94 16.47 16.47 2.35 12.45 12.45 1.17 13.49 13.26 0.82 14.58 14.02 0.54 15.67 14.78 0.33
57
(13.9)
15.28 15.28 2.94 16.44 16.44 2.35 12.43 12.43 1.18 13.39 13.39 0.83 14.36 14.36 0.55 15.33 15.33 0.33
Operation in this area is restricted to maintain reliable system operation and customer comfort. The system will default to the next available stage
Stage 1 - Compressor speed limited to stage two at 105 and 115 outdoor.
See additional notes on page 43