Specifications
PRODUCT SPECIFICATIONS Split System Heat Pump: HVH8
428 51 5900 03 17
Specifications subject to change without notice.
HVH825
DETAILED COOLING CAPACITIES
#
− EFFICIENCY MODE
EDB
°F (°C)
EVAP.
AIR
HVH825 / FCM4X48***L Efficiency Mode
Condenser Entering Air Temperature °F (°C)
115 (46.1) 105 (40.5) 95 (35) 85 (29.4) 75 (23.9) 65 (18.3)
EWB
°F (°C)
ID
SCF
M
Capacity MBtuh Total
Sys.
KW**
ID
SCF
M
Capacity MBtuh Total
Sys.
KW**
ID
SCF
M
Capacity MBtuh Total
Sys.
KW**
ID
SCF
M
Capacity MBtuh Total
Sys.
KW**
ID
SCF
M
Capacity MBtuh Total
Sys.
KW**
ID
SCF
M
Capacity MBtuh Total
Sys.
KW**
Total
Sens
‡
Total
Sens
‡
Total
Sens
‡
Total
Sens
‡
Total
Sens
‡
Total
Sens
‡
STAGE 5
75
(23.9)
72
(22.2)
825
23.61 9.88 2.53
825
25.24 10.47 2.23
825
26.64 10.98 1.92
825
28.18 11.54 1.66
825
29.67 12.09 1.41
825
31.12 12.64 1.18
67
(19.4)
21.33 13.74 2.50 22.80 14.32 2.22 24.06 14.87 1.92 25.46 15.46 1.67 26.82 16.05 1.43 28.12 16.59 1.21
63
(17.2)
19.66 16.76 2.48 21.01 17.35 2.21 22.17 17.92 1.92 23.46 18.51 1.67 24.71 19.11 1.44 25.92 19.72 1.23
57
(13.9)
18.72 18.72 2.47 19.79 19.79 2.20 20.71 20.71 1.91 21.71 21.71 1.67 22.67 22.67 1.45 23.60 23.60 1.24
80
(26.7)
72
(22.2)
825
23.53 13.78 2.53
825
25.17 14.37 2.23
825
26.56 14.92 1.92
825
28.10 15.50 1.66
825
29.60 16.09 1.41
825
31.02 16.63 1.18
67
(19.4)
21.28 17.58 2.50 22.75 18.19 2.22 24.00 18.75 1.92 25.40 19.35 1.67 26.74 19.96 1.43 28.05 20.56 1.21
63
(17.2)
20.03 20.03 2.49 21.17 21.09 2.21 22.29 21.72 1.92 23.54 22.34 1.67 24.78 22.95 1.44 25.96 23.61 1.23
57
(13.9)
19.99 19.99 2.49 21.10 21.10 2.21 22.06 22.06 1.91 23.08 23.08 1.67 24.09 24.09 1.44 25.06 25.06 1.23
STAGE 3
75
(23.9)
72
(22.2)
650
15.43 6.56 1.50
650
16.55 6.96 1.36
650
17.40 7.27 1.13
650
18.52 7.59 0.97
650
19.58 8.06 0.82
650
20.65 8.45 0.67
67
(19.4)
13.88 9.30 1.50 14.90 9.71 1.36 15.70 10.04 1.14 16.69 10.46 0.99 17.67 10.87 0.85 18.63 11.27 0.71
63
(17.2)
12.80 11.44 1.50 13.73 11.87 1.37 14.47 12.22 1.14 15.39 12.65 1.00 16.27 13.10 0.87 17.17 13.48 0.73
57
(13.9)
12.38 12.38 1.50 13.13 13.13 1.37 13.73 13.73 1.14 14.44 14.44 1.01 15.14 15.14 0.88 15.81 15.81 0.76
80
(26.7)
72
(22.2)
650
15.37 9.34 1.50
650
16.49 9.75 1.36
650
17.33 10.09 1.13
650
18.42 10.48 0.97
650
19.51 10.89 0.82
650
20.58 11.27 0.67
67
(19.4)
13.87 12.03 1.50 14.88 12.46 1.36 15.67 12.80 1.14 16.66 13.25 0.99 17.62 13.69 0.85 18.59 14.08 0.71
63
(17.2)
13.28 13.28 1.50 14.07 14.07 1.37 14.69 14.69 1.14 15.58 15.21 1.00 16.44 15.74 0.87 17.23 16.25 0.73
57
(13.9)
13.26 13.26 1.50 14.04 14.04 1.37 14.66 14.66 1.14 15.42 15.42 1.00 16.14 16.14 0.87 16.85 16.85 0.74
STAGE 1
75
(23.9)
72
(22.2)
650
11.91 5.24 1.08
650
12.82 5.56 1.00
585
10.38 4.52 0.57
585
11.19 4.70 0.49
585
11.92 5.07 0.40
585
12.67 5.34 0.30
67
(19.4)
10.68 7.75 1.09 11.52 8.07 1.01 9.32 6.60 0.59 10.00 6.88 0.52 10.68 7.16 0.44 11.35 7.44 0.35
63
(17.2)
9.85 9.65 1.09 10.61 10.02 1.02 8.58 8.20 0.60 9.20 8.49 0.54 9.81 8.79 0.47 10.41 9.08 0.38
57
(13.9)
9.79 9.79 1.09 10.43 10.43 1.02 8.47 8.47 0.60 8.98 8.98 0.54 9.48 9.48 0.48 9.96 9.96 0.40
80
(26.7)
72
(22.2)
650
11.85 7.79 1.08
650
12.79 8.13 1.00
585
10.33 6.64 0.57
585
11.10 6.91 0.49
585
11.86 7.20 0.40
585
12.62 7.48 0.30
67
(19.4)
10.87 9.78 1.09 11.51 10.58 1.01 9.33 8.66 0.58 10.00 8.96 0.52 10.67 9.26 0.44 11.33 9.56 0.35
63
(17.2)
10.56 10.56 1.09 11.24 11.24 1.02 9.12 9.12 0.59 9.67 9.67 0.52 10.20 10.20 0.45 10.72 10.72 0.37
57
(13.9)
10.54 10.54 1.09 11.22 11.22 1.02 9.11 9.11 0.59 9.65 9.65 0.52 10.18 10.18 0.45 10.69 10.69 0.37
Operation in this area is restricted to maintain reliable system operation and customer comfort. The system will default to the next available stage
Stage 1 - Compressor speed limited to stage two at 105 and 115 outdoor.