Application Guidelines

ICP Inverter Heat Pump System Matching with Existing Indoor Equipment
ICP Inverter
Heat Pump
w/ Existing Indoor
System
Fan Coil or
Furnace?
Fan Coil
Furnace
2006-Present or
1992-2005?
Not Compatible
Before 1992
Multi-Stage or
Single Stage
Fan Coil?
Multi-Stage or
Single Stage
Fan Coil?
2006
Present
1992-
2005
VS, 2-Stage Non
Communicating,
or Single Stage?
Backward Compatible to any Observer Capable
furnace
Wi-Fi Observer Control with Version 5.0 software or
newer for Communicating Operation
Full functionality with upgraded Wi-Fi Observer
Control
2-Stage Operation with 2-Stage Thermostat
Check AHRI Ratings for current furnaces
High Speed Airflow; 350-400 cfm/ton
Low Speed Airflow; 70-80% of High Stage
1-Stage Operation until Indoor can be upgraded
1-Stage Operation with 1-Stage Thermostat
Set airflow to 350-400 cfm / ton
Variable Speed
Communicating
2-Stage
Non-Communicating
Single
Stage
Indoor Coil
2006-Present or
1992-2005?
Not Compatible
Before 1992
2006
Present
1992-
2005
See ratings for FVM4, FCM4 matches*
5 stages with FCM4 and Wi-Fi Observer Control
with Version 5.0 software or newer
2 stages with FVM4 and 2-stage thermostat
R-410A refrigerant TXV required on indoor
*2 and 3 ton outdoor unit not compatible with 60
size fan coil
Straight Match or one
size larger than outdoor
tonnage
R-410A Refrigerant TXV
required
Must be 1 or 2 sizes
larger than outdoor
tonnage
R-410A Refrigerant TXV
required
Multi-Stage
Fan Coil
One stage of operation with thermostat until
indoor can be replaced
Straight match or one size larger indoor
R-410A refrigerant TXV required on indoor
Wire as single stage unit.
Set Airflow to 350-400 cfm/ton
Single-Stage
Fan Coil
Multi-Stage
Fan Coil
Single-Stage
Fan Coil
See ratings for FCM4 matches
5 Stage with FCM4 fan coil and Wi-Fi Observer
Control with Version 5.0 software or newer
FVM4 - match size same as current FV*
R-410A refrigerant TXV required on indoor
2 stages with FVM4 and 2-stage stat
*2 and 3 ton not compatible with 60 size fan coil
One stage of operation until indoor can be upgraded
Indoor must be one size larger than outdoor
R-410A refrigerant TXV required on indoor
Wire as single stage unit
Set Airflow to 350-400 cfm/ton
* Examples
Straight matched to outdoor unit tonnage
3-ton ICP Inverter with 3-ton furnace or fan
coil
1 size larger indoor 3-ton ICP Inverter with
3.5 ton furnace or fan coil
2 sizes larger indoor 3-ton ICP Inverter with
older 4 ton furnace coil