Application Guidelines

Existing 1-stage indoor equipment
The ICP inverter will work with a 1-stage thermostat as a 1-stage system with
suitable indoor coil and fan until the indoor components can be upgraded to
provide full variable speed functionality.
Fan coil application if the fan coil was built in 2006 or after, it may be straight
matched or one size larger than the outdoor unit tonnage*. If built between 2005
and 1992, the fan coil must be one size larger than the outdoor unit tonnage*. An
R410A TXV is required on the indoor coil.
Furnace coil application if the furnace coil was built in 2006 or after, it may be
straight matched or one size larger than the outdoor unit tonnage*. If built
between 2005 and 1992, the furnace coil must be one or two sizes larger than
the outdoor unit tonnage*. An R410A TXV is required on the indoor coil.
Set airflow at 350-400 cfm/ton
Line set limitations
The ICP inverter is qualified for line sets up to 100ft equivalent length.
Lift limitations:
Outdoor above indoor: 100 ft.
Outdoor below indoor:
2 ton
3 ton
4 ton
5 ton
80ft
80ft
70ft
60ft
See Product Data for line set diameter requirements
* Examples
Straight matched to outdoor unit tonnage- 3-ton ICP inverter with 3-ton furnace or fan coil
One size larger indoor 3-ton ICP Inverter with 3.5 ton furnace or fan coil
2 sizes larger indoor 3-ton ICP inverter with older 4 ton furnace coil