Installation Manual
22 428 01 5700 02
Specifications subject to change without notice.
LEGEND FOR COOLING:
† Total capacities are net (I.D blower heat subtracted) system capacities based on 25' line set.
If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.
* System amps are total of indoor and outdoor amps
‡ S/T are based on 80 F db entering air at the indoor coil. For sensible capacities at other than 80 F db, deduct 835 Btuh per 1000 cfm
of indoor coil air from MBhxS/T for each degree below 80 F, o r add 835 Btuh per 1000 cfm of indoor coil air from MBhxS/T for each de-
gree above 80 F
†† At TVA rating indoor condition (75 F db/ 63 F wb), All other indoor air temperatures are at 80 F db
# System runs Stage 5 Efficiency Mode for Comfort+dh Mode at 115 degrees F outdoor temperature.
LEGEND FOR HEATING:
† Total capacities are net (I.D blower heat added) system capacities based on 25' line set.
If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.
* System amps are total of indoor and outdoor amps
T/R - Temp Rise is based on 25' line set.
If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in Temp Rise may occur.