Specifications

PRODUCT SPECIFICATIONS Split System Heat Pump: HVH8
5 428 51 5900 03
Specifications subject to change without notice.
PHYSICAL DATA
UNIT SIZE SERIES 24 25 36 37 48 60
Compressor Type Variable Speed Rotary
REFRIGERANT R-410A
Control TXV (R-410A Hard Shutoff)
Charge lb (kg) 5.40 (2.45) 6.38 (2.89) 6.38 (2.89) 7.5 (3.40) 8.30 (3.76) 8.60 (3.90)
Outdoor Htg Exp. Device EXV
COND FAN Forward Swept Propeller Type, Direct Drive
Air Discharge Vertical
Air Qty (CFM) 2080 2500 2500 3800 4500 4500
Motor HP 1/5 1/3 1/3 1/3 1/3 1/3
Motor RPM 825 1050 1050 750 850 900
COND COIL
Face Area (Sq ft) 11.12 13.90 13.90 21.50 21.50 23.65
Fins per In. 20 20 20 20 20 20
Rows 1 1 1 1 1 1
Circuits 5 6 6 8 8 8
VALVE CONNECT. (In. ID)
Vapor 5/8 3/4 3/4 7/8 7/8 7/8
Liquid 3/8
REFRIGERANT TUBES (In. OD)
Rated Vapor* 3/4 7/8 7/8 1-1/8 1-1/8 1-1/8
Max Liquid Line 3/8
* Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset.
Note: See unit Installation Instruction for proper installation.
ELECTRICAL DATA
UNIT SIZE-
VOLTAGE, SERIES
V/PH
OPER VOLTS* COMPR FAN
MCA
MAX FUSE ** or
CKT BRK AMPS
MAX MIN LRA RLA FLA
24
208/230
-1-60
253 197
N/A 10.32 0.58 13.50 20
25 N/A 17.70 1.20 23.60 40
36 N/A 18.30 1.20 24.40 40
37 N/A 19.60 1.20 26.00 40
48 N/A 23.90 1.20 31.40 50
60 N/A 31.30 1.40 40.80 60
* Permissible limits of the voltage range at which the unit will operate satisfactorily
** Time-Delay fuse.
FLA - Full Load Amps
LRA - Locked Rotor Amps
MCA - Minimum Circuit Amps
RLA - Rated Load Amps
NOTE: Control circuit is 24-V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2010 requirements of ASHRAE Standards 90.1
CHARGING SUBCOOLING (TXVTYPE EXPANSION DEVICE)
UNIT SIZE-VOLTAGE, SERIES
Subcooling recommendation displayed in the subcooling chart shown on
the charging label must be followed
24
25
36
37
48
60