Specifications

PRODUCT SPECIFICATIONS Split System Heat Pump: HVH8
428 51 5900 03 45
Specifications subject to change without notice.
HVH860
HEAT PUMP HEATING PERFORMANCE COMFORT MODE
INDOOR AIR
HVH860 / FCM4X60***L Heating Efficiency Mode
Outdoor Coil Entering Air Temperature °F (°C)
7 (-13.9) 17 (-8.3) 27 (-2.8)
EDB
°F (°C)
ID SCFM
Capacity MBtuh
Total Sys. KW† ID SCFM
Capacity MBtuh
Total Sys. KW† ID SCFM
Capacity MBtuh
Total Sys. KW†
Total Integ‡ Total Integ‡ Total Integ‡
STAGE 5
65 (18.3)
840
29.44 27.05 3.99
1600
48.43 44.16 6.49
1600
55.69 49.46 6.61
70 (21.1) 29.47 27.09 4.22 49.06 44.73 7.02 56.12 49.84 7.10
75 (23.3) 29.57 27.17 4.47 49.80 45.40 7.61 56.61 50.28 7.63
STAGE 3
65 (18.3)
700
20.47 18.81 2.46
900
24.06 21.94 2.39
1275
28.38 25.21 2.32
70 (21.1) 20.30 18.66 2.58 23.86 21.75 2.51 28.08 24.94 2.44
75 (23.3) 20.25 18.60 2.73 23.67 21.58 2.64 27.78 24.68 2.56
STAGE 1
65 (18.3)
700
20.47 18.81 2.46
900
24.06 21.93 2.39
1275
21.17 18.80 1.57
70 (21.1) 20.31 18.66 2.58 23.85 21.75 2.51 20.88 18.55 1.56
75 (23.3) 20.27 18.62 2.73 23.66 21.57 2.64 20.60 18.30 1.65
INDOOR AIR
HVH860 / FCM4X60***L Heating Efficiency Mode
Outdoor Coil Entering Air Temperature °F (°C)
37 (2.8) 47 (8.3) 57 (13.9)
EDB
°F (°C)
ID SCFM
Capacity MBtuh
Total Sys. KW† ID SCFM
Capacity MBtuh
Total Sys. KW† ID SCFM
Capacity MBtuh
Total Sys. KW†
Total Integ‡ Total Integ‡ Total Integ‡
STAGE 5
65 (18.3)
1600
64.63 58.81 6.84
1600
73.25 73.25 7.06
1400
43.82 43.82 2.61
70 (21.1) 64.85 59.01 7.31 73.27 73.27 7.50 43.06 43.06 2.72
75 (23.3) 65.13 59.27 7.81 73.33 73.33 7.98 42.35 42.35 2.83
STAGE 3
65 (18.3)
1275
33.13 30.14 2.42
1275
38.00 38.00 2.52
1400
43.82 43.82 2.61
70 (21.1) 32.71 29.76 2.53 37.45 37.45 2.63 43.06 43.06 2.72
75 (23.3) 32.29 29.38 2.65 36.91 36.91 2.75 42.35 42.35 2.83
STAGE 1
65 (18.3)
1275
24.69 22.46 1.57
900
16.76 16.76 0.84
900
19.39 19.39 0.96
70 (21.1) 24.31 22.12 1.66 16.40 16.40 0.93 18.97 18.97 1.06
75 (23.3) 23.94 21.78 1.76 16.04 16.04 1.02 18.56 18.56 1.16
Operation in this area is restricted to maintain reliable system operation and customer comfort. The system will default to the next available stage
Stage 5 - Compressor speed limited to stage four at 7 and stage three at 57 outdoor; Stage 1 - Compressor speed limited to stage three at 7 and 17 and to stage two at 27 and 37 outdoor.
NOTES:
* Tested combination.
{ The kW values include the compressor, outdoor fan motor, and indoor
blower motor. The kW from supplement heaters should be added to
these values to obtain total system kilowatts.
}The Btuh heating capacity values shown are net integrated values from
which the defrost effect has been subtracted. The Btuh heating from
supplement heaters should be added to those values to obtain total
system capacity.
NOTE: When the required data falls between the published data,
interpolation may be performed. Extrapolation is not an acceptable
practice.
EDB — Entering Dry Bulb