Specifications

PRODUCT SPECIFICATIONS Split System Heat Pump: HVH8
428 51 5900 03 41
Specifications subject to change without notice.
HVH860
DETAILED COOLING CAPACITIES
#
EFFICIENCY MODE
EDB
°F
(°C)
EVAP.
AIR
HVH860 / FCM4X60***L Efficiency Mode
Condenser Entering Air Temperature °F (°C)
115 (46.1) 105 (40.5) 95 (35) 85 (29.4) 75 (23.9) 65 (18.3)
EWB
°F
(°C)
ID
SCF
M
Capacity MBtuh
Total
Sys.
KW**
ID
SCF
M
Capacity MBtuh
Total
Sys.
KW**
ID
SCF
M
Capacity MBtuh
Total
Sys.
KW**
ID
SCF
M
Capacity MBtuh
Total
Sys.
KW**
ID
SCF
M
Capacity MBtuh
Total
Sys.
KW**
ID
SCF
M
Capacity MBtuh
Total
Sys.
KW**
Total
Sens
Total
Sens
Total
Sens
Total
Sens
Total
Sens
Total
Sens
STAGE 5
75
(23.9)
72
(22.2)
1600
54.16 21.71 7.27
1600
58.13 23.22 6.50
1600
62.05 24.71 5.83
1600
65.88 26.19 5.23
1600
69.70 27.67 4.69
1600
73.51 29.16 4.22
67
(19.4)
49.48 29.16 7.08 53.10 30.83 6.32 56.62 32.47 5.65 60.10 34.10 5.06 63.54 35.73 4.54 66.97 37.36 4.08
63
(17.2)
46.01 35.04 6.94 49.36 36.81 6.19 52.62 38.56 5.52 55.84 40.30 4.93 59.02 42.03 4.42 62.18 43.77 3.96
57
(13.9)
42.15 42.15 6.80 44.79 44.79 6.03 47.47 47.22 5.36 50.24 49.26 4.78 53.01 51.19 4.27 55.79 53.12 3.82
80
(26.7)
72
(22.2)
1600
54.02 29.01 7.27
1600
57.99 30.66 6.51
1600
61.91 32.31 5.83
1600
65.73 33.94 5.23
1600
69.54 35.58 4.69
1600
73.38 37.25 4.22
67
(19.4)
49.35 36.40 7.08 52.97 38.20 6.32 56.50 39.99 5.65 59.97 41.75 5.06 63.42 43.53 4.54 66.85 45.31 4.08
63
(17.2)
45.98 42.19 6.95 49.31 44.12 6.19 52.56 46.03 5.52 55.76 47.91 4.94 58.94 49.79 4.42 62.09 51.68 3.96
57
(13.9)
44.59 44.59 6.89 47.37 47.37 6.12 50.06 50.06 5.44 52.70 52.70 4.85 55.28 55.28 4.33 57.84 57.84 3.87
STAGE 3
75
(23.9)
72
(22.2)
1350
35.59 14.62 3.53
1350
38.22 15.60 3.17
1350
40.53 16.44 2.81
1350
43.15 17.42 2.52
1350
45.75 18.40 2.26
1350
48.31 19.37 2.03
67
(19.4)
32.14 20.20 3.49 34.58 21.25 3.13 36.71 22.19 2.76 39.08 23.23 2.48 41.41 24.27 2.22 43.72 25.33 1.99
63
(17.2)
29.59 24.58 3.46 31.84 25.69 3.11 33.86 26.69 2.73 36.06 27.78 2.44 38.24 28.87 2.19 40.37 29.94 1.96
57
(13.9)
27.84 27.84 3.44 29.62 29.62 3.09 31.23 31.23 2.70 32.94 32.94 2.42 34.60 34.60 2.16 36.29 36.28 1.94
80
(26.7)
72
(22.2)
1350
35.48 20.25 3.53
1350
38.16 21.30 3.17
1350
40.41 22.20 2.81
1350
43.03 23.25 2.52
1350
45.63 24.29 2.26
1350
48.16 25.35 2.03
67
(19.4)
32.03 25.76 3.49 34.46 26.87 3.13 36.60 27.89 2.76 38.97 28.99 2.48 41.31 30.09 2.22 43.64 31.19 1.99
63
(17.2)
29.79 29.79 3.46 31.90 31.19 3.11 33.89 32.31 2.73 36.06 33.48 2.45 38.22 34.66 2.19 40.34 35.78 1.96
57
(13.9)
29.73 29.73 3.46 31.58 31.58 3.11 33.26 33.26 2.72 35.03 35.03 2.44 36.78 36.78 2.18 38.50 38.50 1.95
STAGE 1
75
(23.9)
72
(22.2)
1200
26.64 11.15 2.26
1200
28.72 11.89 2.04
975
21.20 8.81 1.13
975
22.74 9.36 0.98
975
24.22 9.89 0.82
975
25.66 10.41 0.64
67
(19.4)
23.82 15.66 2.25 25.70 16.41 2.04 18.84 12.09 1.11 20.25 12.62 0.97 21.61 13.15 0.82 22.93 13.66 0.65
63
(17.2)
21.78 19.18 2.24 23.51 19.96 2.03 17.10 14.65 1.10 18.39 15.16 0.97 19.66 15.66 0.82 20.87 16.17 0.66
57
(13.9)
20.87 20.87 2.23 22.22 22.22 2.03 16.17 16.17 1.10 17.13 17.13 0.97 18.04 18.04 0.83 18.90 18.90 0.68
80
(26.7)
72
(22.2)
1200
26.55 15.78 2.26
1200
28.63 16.54 2.04
975
21.10 12.29 1.13
975
22.65 12.79 0.98
975
24.14 13.29 0.82
975
25.57 13.80 0.64
67
(19.4)
23.75 20.23 2.25 25.64 21.01 2.04 18.79 15.49 1.11 20.19 16.00 0.97 21.54 16.51 0.82 22.86 17.00 0.65
63
(17.2)
22.48 22.48 2.24 23.92 23.92 2.03 17.50 17.50 1.11 18.50 18.45 0.97 19.71 19.00 0.82 20.90 19.49 0.66
57
(13.9)
22.45 22.45 2.24 23.87 23.87 2.03 17.47 17.47 1.11 18.45 18.45 0.97 19.40 19.40 0.82 20.29 20.29 0.67
Operation in this area is restricted to maintain reliable system operation and customer comfort. The system will default to the next available stage
Stage 1 - Compressor speed limited to stage two at 105 and 115 outdoor.
See additional notes on page 43