Specifications

PRODUCT SPECIFICATIONS Split System Heat Pump: HVH8
428 51 5900 03 39
Specifications subject to change without notice.
HVH848
HEAT PUMP HEATING PERFORMANCE COMFORT MODE
INDOOR AIR
HVH860 / FCM4X60***L Heating Comfort Mode
Outdoor Coil Entering Air Temperature °F (°C)
7 (-13.9) 17 (-8.3) 27 (-2.8)
EDB
°F (°C)
ID SCFM
Capacity MBtuh
Total Sys. KW† ID SCFM
Capacity MBtuh
Total Sys. KW† ID SCFM
Capacity MBtuh
Total Sys. KW†
Total Integ‡ Total Integ‡ Total Integ‡
STAGE 5
65 (18.3)
600
22.44 20.62 2.78
934
34.33 31.30 3.70
1139
39.97 35.50 3.80
70 (21.1) 20.06 18.43 2.60 33.36 30.42 3.99 40.36 35.85 4.06
75 (23.3) 20.34 18.69 2.57 32.54 29.67 3.83 39.62 35.19 4.44
STAGE 3
65 (18.3)
450
16.76 15.40 2.15
633
20.49 18.68 2.24
724
23.71 21.06 2.29
70 (21.1) 15.82 14.54 2.03 20.28 18.49 2.36 23.55 20.92 2.43
75 (23.3) 15.13 13.91 2.12 19.73 17.99 2.41 23.38 20.76 2.56
STAGE 1
65 (18.3)
450
16.80 15.44 2.16
569
20.44 18.64 2.30
629
19.82 17.60 1.98
70 (21.1) 16.51 15.17 2.43 20.20 18.42 2.41 20.00 17.77 1.98
75 (23.3) 13.93 12.80 2.31 18.49 16.86 2.70 19.83 17.61 2.09
INDOOR AIR
HVH860 / FCM4X60***L Heating Comfort Mode
Outdoor Coil Entering Air Temperature °F (°C)
37 (2.8) 47 (8.3) 57 (13.9)
EDB
°F (°C)
ID SCFM
Capacity MBtuh
Total Sys. KW† ID SCFM
Capacity MBtuh
Total Sys. KW† ID SCFM
Capacity MBtuh
Total Sys. KW†
Total Integ‡ Total Integ‡ Total Integ‡
STAGE 5
65 (18.3)
1344
45.25 41.18 4.09
1550
50.80 50.80 4.12
996
35.14 35.14 2.47
70 (21.1) 45.69 41.58 4.37 51.38 51.38 4.42 34.47 34.47 2.34
75 (23.3) 46.09 41.94 4.66 51.92 51.92 4.74 34.72 34.72 2.52
STAGE 3
65 (18.3)
814
27.37 24.91 2.37
905
31.23 31.23 2.43
996
35.14 35.14 2.47
70 (21.1) 27.16 24.72 2.51 30.96 30.96 2.58 34.84 34.84 2.62
75 (23.3) 26.96 24.54 2.66 30.69 30.69 2.73 34.50 34.50 2.78
STAGE 1
65 (18.3)
690
23.02 20.95 2.06
350
15.27 15.27 1.19
403
17.49 17.49 1.15
70 (21.1) 22.56 20.53 2.16 14.75 14.75 1.17 16.87 16.87 1.22
75 (23.3) 22.78 20.73 2.16 14.36 14.36 1.23 16.27 16.27 1.20
Operation in this area is restricted to maintain reliable system operation and customer comfort. The system will default to the next available stage
Stage 5 - Compressor speed limited to stage four at 7 and stage three at 57 outdoor; Stage 1 - Compressor speed limited to stage three at 7 and 17 and to stage two at 27 and 37 outdoor.
See additional notes on page 45