Installation Manual
75
616 01 1019 01
On the heating screen, there are three (3) selectable items.
S Maximum Cooling Stage
S Minimum Cooling Stage
S Threshold Outdoor Air Temperature above which the
minimum heating stage is applied.
NOTE: The available stages the equipment is able to r un is
dynamic with respect to outdoor air temperature. If range of
available stages is outside of the dealer-selectable, minimum
and maximum stage limits, the limts will be temporarily over-
riden. If the minimum available stage is above a
corresponding maximum limit, then the minimum available
stage will be allowed to run. Likewise if the maximum
available stage is below a corresponding minimum limit, then
the maximum available stage will be allowed to run.